Inspections for the day of: Wednesday, July 22, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02257 Temporary Service7/21/20157/22/20157/23/2015 12:58:10 PMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
ELE15-01698 Final7/22/20157/22/20157/22/2015 2:39:09 PMPFAIL
Homeowners will be on site. Phone #: ###-#### Inspection requested via web by Paula Gratiot 210.12 (a) arc fault protection for required for bedrooms
ELE15-02218 Electrical Rough-In7/21/20157/22/20157/22/2015 2:09:34 PMPPASS
I''ll be ready by noon. Phone #: ###-#### Inspection requested via web by Andy Derrick kitchen rough-in ok cover
ELE15-02015 Electrical Rough-In7/21/20157/22/20157/22/2015 1:49:25 PMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL cieling rough-in ok cover
ELE15-02183 Final7/20/20157/22/20157/22/2015 1:17:51 PMAPASS
Hey Eric, Just a heads up, the home owner will not be home, so give me a call a couple hours before you head out, and I''ll meet you there. 850.8965

But here''s what you''ll be checking out -

10 solar panels.
AC micro-inverter system. No DC voltage.
Enphase M250 Micro-Inverters, that are CSA, IEEE-1547, and UL-1741 listed.
Ironridge Integrated Grounding System mid clamps, bonding straps and bonding lugs.
And 275 watt Suniva panels, ETL listed.

A single home run, in metal conduit, is ran from the solar array to the knife switch, located next to meter base on west side of home. From the knife switch to breaker in main panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are permanently marked for solar, and the circuit numbers identified in the knife switch and on the panel schedule.

The inverters, panels and rails are all bonded with a number 6 ground that runs back to the service grounding electrode in the main panel.

Thanks Phone #: ###-#### Inspection requested via web by Ryan King final for photovoltaic system ok
ELE15-02183 Electrical Rough-In7/22/20157/22/20157/22/2015 1:17:11 PMPPASS
Hey Eric, Just a heads up, the home owner will not be home, so give me a call a couple hours before you head out, and I''ll meet you there. 850.8965

But here''s what you''ll be checking out -

10 solar panels.
AC micro-inverter system. No DC voltage.
Enphase M250 Micro-Inverters, that are CSA, IEEE-1547, and UL-1741 listed.
Ironridge Integrated Grounding System mid clamps, bonding straps and bonding lugs.
And 275 watt Suniva panels, ETL listed.

A single home run, in metal conduit, is ran from the solar array to the knife switch, located next to meter base on west side of home. From the knife switch to breaker in main panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are permanently marked for solar, and the circuit numbers identified in the knife switch and on the panel schedule.

The inverters, panels and rails are all bonded with a number 6 ground that runs back to the service grounding electrode in the main panel.

Thanks Phone #: ###-#### Inspection requested via web by Ryan King rough-in for photovoltaic verified ul listing and grounding ok
ELE15-01343 Electrical Rough-In7/22/20157/22/20157/22/2015 12:37:57 PMPPASS
Floor heat install
After 2:00 if possible Phone #: ###-#### Inspection requested via web by Emmet Bushman rough-in master floor heat ok cover
ELE15-02020 Final7/22/20157/22/20157/22/2015 12:23:11 PMPPASS
Mitch Phone #: ###-#### service change final ok
ELE15-01704 Electrical Rough-In7/22/20157/22/20157/22/2015 11:02:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Jarod Murray rough-in ok cover
ELE15-02255 Electrical Rough-In7/21/20157/22/20157/22/2015 10:42:59 AMAPASS
Some one will be home, if you have any questions, please call Calvin. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan basement remodel rough-in ok cover
ELE15-02227 Electrical Rough-In7/21/20157/22/20157/22/2015 10:23:06 AMAPASS
Jim Phone #: ###-#### kitchen-dinning room-bath-back bedroom rough-in ok cover
ELE15-02099 Permanent Service7/21/20157/22/20157/22/2015 10:01:39 AMAPASS
Was pull for temp service when it should have been a Permanent Service. Fees are due before permit can be finaled. If questions please call Darly D ###-#### PermanPhone #: ###-#### Inspection requested via web by Krista Ratterree p/s o/h n ok
ELE15-02254 Final7/21/20157/22/20157/22/2015 10:00:33 AMACANC
Phone #: ###-#### Inspection requested via web by daniel bibikov no access homeowner not home