Inspections for the day of: Monday, September 23, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02953 Final9/23/20199/23/20199/23/2019 3:24:02 PMPPASS
Electrician is Chris. Phone #: ###-#### Inspection requested via web by Same Electric
Final ok
ELE18-01007 Final9/23/20199/23/20199/23/2019 2:51:07 PMPFAIL
Call ahead // Russ Phone #: ###-####
1)Non-tamper installed in isc areas throughout house
2) Lockout for dishwasher
3)AFCI protection for bedrooms not GFCI
4) protect NM cables when exposed to physical damage
ELE19-00030 Electrical Rough-In9/23/20199/23/20199/23/2019 2:21:45 PMPPASS
Room behind electrical ok to cover
ELE19-00030 Permanent Service9/23/20199/23/20199/23/2019 2:20:39 PMPCANC
Journeyman on-site, Wade Luthy, ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins
AFC needs re-calculated and posted
ELE19-01628 Electrical Rough-In9/23/20199/23/20199/23/2019 1:40:09 PMPPASS
This request is for a partial rough/cover inspection for the common areas and stairwells, Please call Jerry with any questions he will be onsite, ###-#### Phone #: ###-#### Inspection requested via web by Darryn Coburn
Comm areas and stairways and halls throughout ok to cover(areas as noted will be one sided)
ELE19-02266 Electrical Rough-In9/20/20199/23/20199/23/2019 10:28:50 AMACANC
SERVICE GROUND INSPECTION. CONTACT IS DEREK BALL. Phone #: ###-#### Inspection requested via web by Scott Campbell
Needed p/s
ELE19-02266 Permanent Service9/23/20199/23/20199/23/2019 10:09:06 AMPPASS
SERVICE GROUND INSPECTION. CONTACT IS DEREK BALL. Phone #: ###-#### Inspection requested via web by Scott Campbell
AFC posted 7,624
p/s u/g n ok 2 meters
ELE19-03574 Final9/20/20199/23/20199/23/2019 9:51:35 AMAPASS
Robert Phone #: ###-####
Mini split final ok
ELE19-03382 Final9/20/20199/23/20199/23/2019 9:29:56 AMAPASS
Please call Zach (Home owner) at 5096073830 before heading to location. Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
Mini split unit final ok
ELE19-03527 Permanent Service9/18/20199/23/20199/23/2019 8:12:05 AMPCANC
Call Fred with any questions ###-#### Phone #: ###-#### >> Inspection requested via web by Clayton Morgan Inspection cancelled from web by: Clayton Morgan