ELE13-00310 ELE-Aging Inspection9/9/20159/9/20159/15/2015 7:53:51 AM CANC
too busy
ELE15-02781 Permanent Service9/4/20159/9/20159/9/2015 1:53:03 PMPPASS
220A Service Upgrade ; Spa Connection. Idaho Power to disconnect at 10am. Phone #: ###-#### Inspection requested via web by Louis Keller p/s o/h rec ok
ELE15-02819 Conference9/8/20159/9/20159/9/2015 1:52:18 PMPDONE
To discuss service Phone #: ###-#### Inspection requested via web by kendall bender discussed moving overhead mast to the south for install of a deck. maintian 3' from windows
GCE15-00139 GCE-Rough-In9/9/20159/9/20159/9/2015 12:50:39 PMPDONE
CONFERENCE ONLY - Roger ###-#### discussed wiring of sunroom and receptacles locations and feeding circuits from existing subpanel outside
GCE15-00143 GCE-Temporary Service9/9/20159/9/20159/9/2015 12:05:18 PMPPASS
Greg ###-#### t/s u/g n ok
ELE15-02399 Final9/8/20159/9/20159/9/2015 10:54:15 AMAFAIL
Mike// prefers late morning Phone #: ###-#### 210.8 all 120v receptacles located in a bathroom shall have gfci protetion 422.31 permanetly installed appliances shall have a locking device (water heater and dishwasher) 240.24 (f) overcurrent devices shall not be located over a step of a stairway 110.26 (1) must maintain 36" working clearences of live parts
ELE15-02652 Final9/8/20159/9/20159/9/2015 10:07:36 AMAPASS
Call Wade Fitzgerald at ###-#### and he will meet you on site to walk you through the system. Phone #: ###-#### Inspection requested via web by Matthew Dunay solar array final ok
ELE15-02853 Electrical Rough-In9/8/20159/9/20159/9/2015 9:42:35 AMAPASS
Contact: Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden storage room and offices 1-5 as per contractors print ok cover
ELE15-02672 Electrical Rough-In9/8/20159/9/20159/9/2015 9:15:35 AMAPASS
this is for partial cover in the hot tub area and kitchen wall call dave with questions
Phone #: ###-#### Inspection requested via web by Don Lustig hot tub and mens and womens bath