Inspections for the day of: Thursday, October 11, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-02649 FIRE-Final Inspection10/10/201210/11/201210/12/2012 2:05:48 PMAFAIL
Correction items include; repair three exit signs/EM lights at the west hangar 101, provide correct size PFE at the office second floor, repair one EM light at the east hangar 101, provide means of free egress at office 102.
FIR12-00352 INSP-Final Inspection10/11/201210/11/201210/12/2012 1:56:27 PMPPART
Lonnie phone #: ###-####
FIR12-00566 INSP-Sprinkler Rough-in10/11/201210/11/201210/12/2012 7:08:58 AMPPART
Overhead fire sprinkler work okay for cover. Spacing adjustment at one location completed while on site. Noted existing system is overdue annual inspection.
BLD12-02261 FIRE-Final Inspection10/11/201210/11/201210/12/2012 7:04:43 AMPNR
BLD12-00472 FIRE-Final Inspection10/11/201210/11/201210/12/2012 7:03:29 AMPFAIL
Smoke alarms on the main level outside the bedrooms do not meet spacing criteria per NFPA 72 ch 29. See also project attatched fire code review notes regarding locations required for smoke alarms.
FIR12-00546 INSP-Final Inspection10/11/201210/11/201210/12/2012 6:58:38 AMPPASS
Fire sprinkler permit finaled.
FIR12-00540 INSP-Final Inspection10/11/201210/11/201210/12/2012 6:56:58 AMPPASS
Fire sprinkler permit finaled.
BLD12-02138 FIRE-Conference10/11/201210/11/201210/12/2012 6:56:03 AMPDONE
Regarding fire sprinkler coverage at the cooler.
BLD12-02663 FIRE-Final Inspection10/10/201210/11/201210/12/2012 6:55:03 AMAPASS
Fire life safety passed. Noted fire extinguishers and the hood suppression system are due certification this November.
FIR11-00560 INSP-Final Inspection10/9/201210/11/201210/12/2012 6:52:36 AMAFAIL
Correction items are incomplete- SD at the panel missing, permit address is inaccurate, autotest trouble on the FACP, and the monitor module for the DSC power supply reported as a supervisory condition.
FIR12-00500 INSP-Sprinkler Rough-in10/10/201210/11/201210/12/2012 6:48:23 AMAPART
Overhead fire sprinkler work approved for cover.