Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00020 INSP-Final Inspection10/29/201210/29/201210/29/2012 5:09:29 PMPPASS
Scope of work completed. Fire sprinkler permit finaled.
FIR12-00323 FIR-Aging Inspection10/29/201210/29/201210/29/2012 5:08:06 PM DEFR
BLD12-01941 FIRE-Final Inspection10/29/201210/29/201210/29/2012 4:58:59 PMPFAIL
Type one hood failed to report to the FACP, modifications to the fire alarm system will be necessary to maintain coverage where new walls and partitions have been built, project related fire sprinkler permit needs called for inspection, noted one EM light to be repaired, relocate the K class PFE as discussed.
FIR12-00604 INSP-Sprinkler Rough-in10/29/201210/29/201210/29/2012 4:50:46 PMPPART
Overhead rough-in inspection completed. Need to verify lintel or door at second floor bathroom to meet ft2 exception or install a pendent, missing sprinkler heads at two locations. Tenting to be inspected prior to approval for cover.
FIR12-00441 INSP-Supply line flush10/29/201210/29/201210/29/2012 4:33:00 PMPNR
FIR12-00335 INSP-Final Inspection10/26/201210/29/201210/29/2012 4:31:14 PMAFAIL
Hood suppression system operated correctly- however the fire alarm panel did not recieve an alarm signal. Final pending repairs.
FIR12-00393 INSP-Final Inspection10/26/201210/29/201210/29/2012 4:25:31 PMAPASS
Coverage adjustments verified. Fire sprinkler permit work complete, permit finaled.