FIR12-00020
| INSP-Final Inspection | 10/29/2012 | 10/29/2012 | 10/29/2012 5:09:29 PM | P | PASS |
|
|
Scope of work completed. Fire sprinkler permit finaled.
|
FIR12-00323
| FIR-Aging Inspection | 10/29/2012 | 10/29/2012 | 10/29/2012 5:08:06 PM | | DEFR |
|
|
|
BLD12-01941
| FIRE-Final Inspection | 10/29/2012 | 10/29/2012 | 10/29/2012 4:58:59 PM | P | FAIL |
|
|
Type one hood failed to report to the FACP, modifications to the fire alarm system will be necessary to maintain coverage where new walls and partitions have been built, project related fire sprinkler permit needs called for inspection, noted one EM light to be repaired, relocate the K class PFE as discussed.
|
FIR12-00604
| INSP-Sprinkler Rough-in | 10/29/2012 | 10/29/2012 | 10/29/2012 4:50:46 PM | P | PART |
|
|
Overhead rough-in inspection completed. Need to verify lintel or door at second floor bathroom to meet ft2 exception or install a pendent, missing sprinkler heads at two locations. Tenting to be inspected prior to approval for cover.
|
FIR12-00441
| INSP-Supply line flush | 10/29/2012 | 10/29/2012 | 10/29/2012 4:33:00 PM | P | NR |
|
|
|
FIR12-00335
| INSP-Final Inspection | 10/26/2012 | 10/29/2012 | 10/29/2012 4:31:14 PM | A | FAIL |
|
|
Hood suppression system operated correctly- however the fire alarm panel did not recieve an alarm signal. Final pending repairs.
|
FIR12-00393
| INSP-Final Inspection | 10/26/2012 | 10/29/2012 | 10/29/2012 4:25:31 PM | A | PASS |
|
|
Coverage adjustments verified. Fire sprinkler permit work complete, permit finaled.
|