Inspections for the day of: Thursday, November 21, 2013.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00180 INSP-Final Inspection11/20/201311/21/201311/25/2013 7:23:17 AMAFAIL
Inspection completed 11/21. SD at the elevator lobbies in the new parking garage will not meet listing due to missing HVAC. Provide verification existing fire/smoke dampers are not required or interface with panel per plan. Provide a plan modification due to necessary changes.
BLD13-02534 FIRE-Final Inspection11/21/201311/21/201311/21/2013 4:33:54 PMPPASS
Scope of work passed fire life safety.
FIR13-00434 INSP-Final Inspection11/21/201311/21/201311/21/2013 3:02:28 PMPPASS
Fire sprinkler permit work completed and passed final walkthrough.
BLD13-00724 FIRE-Final Inspection11/20/201311/21/201311/21/2013 2:12:07 PMPPASS
Fire life safety inspection passed.
FIR13-00432 INSP-Supply line flush11/19/201311/21/201311/21/2013 1:06:54 PMAPART
Remainder of UG fire supply line including thrust blocking prior to tie-in okayed for cover.
FIR13-00429 INSP-Sprinkler Rough-in11/20/201311/21/201311/21/2013 11:02:04 AMAPART
Inspection for fire sprinkler work at the hard lid soffits completed per dated annotations- two heads exceed min. separation distances, two heads are not yet cut in due to missing framing, remiander okayed.
FIR13-00523 INSP-Sprinkler Rough-in11/20/201311/21/201311/21/2013 10:58:21 AMAPART
Overhead work at the grid ceilings approved for cover.
FIR13-00657 INSP-Final Inspection11/20/201311/21/201311/21/2013 10:56:41 AMAPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
FIR13-00647 INSP-Sprinkler Rough-in11/20/201311/21/201311/21/2013 9:25:18 AMAPART
Overhead work passed inspection.
FIR12-00310 FIR-Aging Inspection11/21/201311/21/201311/21/2013 9:00:10 AM DEFR
FIR11-00394 FIR-Aging Inspection11/21/201311/21/201311/21/2013 8:59:32 AM DEFR
FIR11-00561 FIR-Aging Inspection11/21/201311/21/201311/21/2013 8:59:11 AM DEFR
FIR12-00311 FIR-Aging Inspection11/21/201311/21/201311/21/2013 8:58:45 AM DEFR
FIR13-00440 INSP-Sprinkler Rough-in11/20/201311/21/201311/21/2013 8:56:43 AMAPART
UG fire supply line and yard PIV at Main street okayed for cover.