FIR13-00180
| INSP-Final Inspection | 11/20/2013 | 11/21/2013 | 11/25/2013 7:23:17 AM | A | FAIL |
|
|
Inspection completed 11/21. SD at the elevator lobbies in the new parking garage will not meet listing due to missing HVAC. Provide verification existing fire/smoke dampers are not required or interface with panel per plan. Provide a plan modification due to necessary changes.
|
BLD13-02534
| FIRE-Final Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 4:33:54 PM | P | PASS |
|
|
Scope of work passed fire life safety.
|
FIR13-00434
| INSP-Final Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 3:02:28 PM | P | PASS |
|
|
Fire sprinkler permit work completed and passed final walkthrough.
|
BLD13-00724
| FIRE-Final Inspection | 11/20/2013 | 11/21/2013 | 11/21/2013 2:12:07 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR13-00432
| INSP-Supply line flush | 11/19/2013 | 11/21/2013 | 11/21/2013 1:06:54 PM | A | PART |
|
|
Remainder of UG fire supply line including thrust blocking prior to tie-in okayed for cover.
|
FIR13-00429
| INSP-Sprinkler Rough-in | 11/20/2013 | 11/21/2013 | 11/21/2013 11:02:04 AM | A | PART |
|
|
Inspection for fire sprinkler work at the hard lid soffits completed per dated annotations- two heads exceed min. separation distances, two heads are not yet cut in due to missing framing, remiander okayed.
|
FIR13-00523
| INSP-Sprinkler Rough-in | 11/20/2013 | 11/21/2013 | 11/21/2013 10:58:21 AM | A | PART |
|
|
Overhead work at the grid ceilings approved for cover.
|
FIR13-00657
| INSP-Final Inspection | 11/20/2013 | 11/21/2013 | 11/21/2013 10:56:41 AM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions. Permit finaled.
|
FIR13-00647
| INSP-Sprinkler Rough-in | 11/20/2013 | 11/21/2013 | 11/21/2013 9:25:18 AM | A | PART |
|
|
Overhead work passed inspection.
|
FIR12-00310
| FIR-Aging Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 9:00:10 AM | | DEFR |
|
|
|
FIR11-00394
| FIR-Aging Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 8:59:32 AM | | DEFR |
|
|
|
FIR11-00561
| FIR-Aging Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 8:59:11 AM | | DEFR |
|
|
|
FIR12-00311
| FIR-Aging Inspection | 11/21/2013 | 11/21/2013 | 11/21/2013 8:58:45 AM | | DEFR |
|
|
|
FIR13-00440
| INSP-Sprinkler Rough-in | 11/20/2013 | 11/21/2013 | 11/21/2013 8:56:43 AM | A | PART |
|
|
UG fire supply line and yard PIV at Main street okayed for cover.
|