Inspections for the day of: Friday, March 2, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01395 FIRE-Final Inspection3/2/20123/2/20123/2/2012 5:06:19 PMPNR
Missing two exit signs, post building address, delayed egress hardware is not yet installed. Discussed general fire life safety requirements.
FIR11-00431 INSP-Sprinkler Rough-in/Hydro3/2/20123/2/20123/2/2012 5:04:13 PMPNR
Deluge valve installation incomplete at this time. Main and branchline including drops in place. Two drops in need of adjustment.
FIR11-00575 INSP-Alarm Testing2/29/20123/2/20123/2/2012 4:56:04 PMPPART
Completed initial walkthrough and partial testing for fire alarm work at sector 30 and sector 40 sub fab mechanical areas. Notification appliances and pull stations tested okay. Noted address needs assigned at the sw stair MP and accurate descriptor provided for the nw MP. Notification coverage in the fabrication areas may become obstructed as more process equipment is installed. Discussed associated permits for tool monitoring, vesdas, added tamper switches. Elevator control functions are incomplete at this time.
FIR12-00074 INSP-Final Inspection3/2/20123/2/20123/2/2012 3:06:26 PMPPASS
Scope of fire alarm work passed field inspection. Permit finaled.
FIR11-00691 INSP-Final Inspection3/1/20123/2/20123/2/2012 3:04:50 PMADEFR
Overbooked
FIR11-00563 INSP-Sprinkler Rough-in/Hydro3/2/20123/2/20123/2/2012 3:02:00 PMAPART
Overhead installation at the 1st floor mechanical room 162, corridor 2A, and electrical 159 okay for cover with the agreement changes in pipe routing at room 162 are approved. Also inspected 2nd floor units 221 thru 224, internet cafe and barber 270. Noted missing coverage at the storage closet in the barber room. See plans for annotations.
FIR11-00178 FIR-Aging Inspection3/2/20123/2/20123/2/2012 1:15:03 PM DONE
Ref. permit activity notes 2/1
FIR11-00216 FIR-Aging Inspection3/2/20123/2/20123/2/2012 12:30:47 PM FAIL
Need contractor final inspection request.
BLD12-00245 FIRE-Final Inspection3/1/20123/2/20123/2/2012 12:22:31 PMAPASS
Correction items field verified. Life safety passed.
FIR11-00527 INSP-Final Inspection3/2/20123/2/20123/2/2012 12:19:01 PMAPASS
Fire sprinkler permit finaled.
BLD12-00331 FIRE-Final Inspection3/1/20123/2/20123/2/2012 12:18:18 PMAPASS
Life safety approved pending door hardware at the main entry/exit (door knob to be removed) Replace with lever style as discussed- to be completed prior to structural final as agreed.
BLD12-00333 FIRE-Final Inspection3/1/20123/2/20123/2/2012 12:13:17 PMAPASS
Fire life safety inspection completed. Tenant to post max. occupant sign at "81" per correction notice and item #10 on the list of general requirements attatched to the permit documents. Remainder of items okayed.
FIR12-00112 INSP-Sprinkler Rough-in3/1/20123/2/20123/2/2012 12:10:26 PMAPART
Overhead work at the remodel area above and below ceilings approved for cover. Note: sheetrock divider adjacent to to the new restroom above storage room to be removed to facilitate upright coverage, annual system inspection is one month past due, missing coverage below existing overhead garage door.