BLD13-00181
| FIRE-Conference | 3/19/2014 | 3/19/2014 | | P | |
|
|
JC at phone #: ###-####
|
FIR13-00713
| INSP-Sprinkler Rough-in | 3/25/2014 | 3/26/2014 | 3/26/2014 4:30:36 PM | A | PART |
|
|
Please schedule a rough for 2nd and 3ed floors. Call Nick 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
|
FIR13-00704
| INSP-Final Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 3:13:47 PM | P | DEFR |
|
|
Scheduled in conjunction with related permit finals 3/27.
|
FIR13-00673
| INSP-Final Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 3:11:56 PM | P | PART |
|
|
Final pending C/N items per C. Hansen.
|
BLD14-00660
| FIRE-Final Inspection | 3/25/2014 | 3/26/2014 | 3/26/2014 3:06:24 PM | P | FAIL |
|
|
Items per plan review annotations are incomplete- need to provide exit signs, egress lighting, PFE, max occ. sign, extend occupant notification, reverse door swing at one location.
|
BLD13-03286
| FIRE-Final Inspection | 3/25/2014 | 3/26/2014 | 3/26/2014 2:22:07 PM | A | FAIL |
|
|
Installation of new doors at the west and south corridors has interupted existing fire sprinkler coverage. Modifications to the fire sprinkler system will be necessary to maintain protection prior to permit final.
|
FIR08-00387
| FIR-Aging Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 11:50:23 AM | | DEFR |
|
|
|
FIR08-00368
| FIR-Aging Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 11:49:37 AM | | DEFR |
|
|
|
FIR03-00411
| FIR-Aging Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 11:48:53 AM | | PASS |
|
|
|
BLD13-03257
| FIRE-Final Inspection | 3/26/2014 | 3/26/2014 | 3/26/2014 11:47:08 AM | A | NR |
|
|
Project related FIR trade work including the fire alarm and sprinkler permit finals pending, need to post signage at the main entry/exit, remove mag lock or provide relay to the fire alarm system at the east exit door, post signage at the courtyard exit door, missing knox box, post signage at the riser room door, noted some exit signs not functional on battery backup. Discussed project schedule for permit finals.
|
FIR13-00440
| INSP-Sprinkler Rough-in | 3/26/2014 | 3/26/2014 | 3/26/2014 11:41:32 AM | A | PART |
|
|
1st floor hard lid areas as marked on plans okay for cover-
|
BLD13-00998
| FIRE-Sprinkler Rough-in | 3/26/2014 | 3/26/2014 | 3/26/2014 11:39:46 AM | A | PART |
|
|
Additions and modifications to the existing fire sprinkler system per the scope of work are approved for cover as noted on the stamped drawings. Tenant to install insulation above the second floor ceiling per plan notes as discussed.
|