Inspections for the day of: Monday, May 5, 2014.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00661 INSP-Final Inspection5/5/20145/5/20145/5/2014 4:27:52 PMPPASS
Fire sprinkler permit work approved for final.
BLD13-01888 FIRE-Final Inspection5/2/20145/5/20145/5/2014 3:45:48 PMPPASS
For previous correction items listed per C. Hanson
FIR14-00197 INSP-Sprinkler Rough-in/Hydro5/5/20145/5/20145/5/2014 2:23:47 PMPPART
Overhead hydrostatic test of the new system main and branchlines passed. Also completed a preliminary rough-in of the new riser manifold, 6" main and 3" branchlines. Tie-ins, demo work, and heads in drop ceilings are not done at this time.
FIR14-00142 INSP-Alarm Testing5/5/20145/5/20145/5/2014 12:23:16 PMADONE
Verified air flow measurements per HVAC contractor at the duct smoke detector using a Fluke 922 meter and pitot.
FIR13-00440 INSP-Sprinkler Rough-in5/5/20145/5/20145/5/2014 12:18:22 PMAPART
Install at plan mod two sheets FP0.1- FP1 passed rough-in.
FIR14-00215 INSP-Sprinkler Rough-in5/5/20145/5/20145/5/2014 12:12:23 PMAPART
Regarding coverage adjustments due to light fixture relocations.