Inspections for the day of: Friday, August 9, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01758 FIRE-Final Inspection8/9/20138/9/20138/9/2013 5:08:13 PMPPASS
Previous correction items verified for completion. Fire life safety inspection passed.
FIR13-00388 INSP-Final Inspection8/9/20138/9/20138/9/2013 5:06:18 PMPPASS
Scope of work finished. Both rough-in and final inspections completed. Fire sprinkler permit finaled.
FIR13-00299 INSP-Sprinkler Rough-in/Hydro8/8/20138/9/20138/9/2013 5:04:38 PMPPART
OH hydrostatic testing for the new system additions completed satisfactory. Also completed rough-in inspection.
FIR13-00297 INSP-Final Inspection8/9/20138/9/20138/9/2013 3:25:31 PMPPASS
Final inspection passed. Fire sprinkler permit finaled.
FIR13-00204 INSP-Sprinkler Rough-in/Hydro8/8/20138/9/20138/9/2013 3:23:09 PMPNR
Hydrostatic test incompleted due to system leakage in need of repair.
FIR13-00268 INSP-Final Inspection8/6/20138/9/20138/9/2013 3:21:10 PMAFAIL
Completed initial walkthrough. Items noted include; provide a MP at stairway #2 second floor exit door, visual notification at ADA rooms to meet guidelines per NFPA 72 table 18.5.4.6.2, adjust cd settings at notification appliances in mech. room 130 and facilities room 137, post signage at the door leading to the FACP per review note #25, post points map including location of the CO detectors, relocate HD at the elevator machine room, provide for shunt trip and include revision on operations matrix. Functional testing pending corrections and adjustments.
FIR08-00368 FIR-Aging Inspection8/9/20138/9/20138/9/2013 3:08:12 PM PEND
FIR08-00387 FIR-Aging Inspection8/9/20138/9/20138/9/2013 3:07:18 PM PEND
FIR08-00825 FIR-Aging Inspection8/9/20138/9/20138/9/2013 3:06:54 PM PEND
FIR13-00268 FIR-Aging Inspection8/6/20138/9/20138/9/2013 3:04:43 PMADONE
Duplicate inspection request
FIR13-00334 INSP-Final Inspection8/8/20138/9/20138/9/2013 3:03:28 PMAPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
FIR13-00037 INSP-Sprinkler Rough-in/Hydro8/7/20138/9/20138/9/2013 3:02:22 PMAPART
Overhead hydrostatic test for the first and second floor wet systems passed.
FIR13-00288 INSP-Sprinkler Rough-in8/8/20138/9/20138/9/2013 2:45:51 PMAPART
Okay to cover overhead fire sprinkler work at project "phase one" as annotated and initialed on stamped plans.