Inspections for the day of: Thursday, September 13, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00019 FIR-Aging Inspection9/13/20129/13/20129/17/2012 4:37:24 PM DONE
FIR11-00690 FIR-Aging Inspection9/13/20129/13/20129/17/2012 4:36:33 PM DONE
FIR11-00680 FIR-Aging Inspection9/13/20129/13/20129/14/2012 2:47:17 PM DONE
Construction underway, site work in progress.
FIR12-00290 INSP-Final Inspection9/12/20129/13/20129/13/2012 5:20:58 PMPNR
Foward flow test did not meet system design.
FIR12-00264 INSP-Final Inspection9/12/20129/13/20129/13/2012 5:16:54 PMPPEND
russ Phone #: ###-####
FIR12-00291 INSP-Final Inspection9/12/20129/13/20129/13/2012 5:15:49 PMPFAIL
Refer to fire code review notes items number 14,15 and 23. Also need to test elevator recall functions when car is operational.
BLD12-01290 FIRE-Final Inspection9/13/20129/13/20129/13/2012 5:08:35 PMPPASS
Fire life safety inspection completed acceptable.
FIR12-00491 INSP-Final Inspection9/13/20129/13/20129/13/2012 5:07:13 PMPFAIL
Fire alarm panel does not report offsite per IFC conditions.
BLD12-02006 FIRE-Conference9/12/20129/13/20129/13/2012 5:00:42 PMPDONE
On site conference with tenant regarding fire sprinkler coverage and NFPA 13 requirements.