Inspections for the day of: Wednesday, September 3, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00487 INSP-Final Inspection8/29/20149/3/20149/3/2014 4:12:46 PMPPASS
Fire alarm permit work passed inspection. Final approved.
FIR14-00508 INSP-Final Inspection9/3/20149/3/20149/3/2014 3:55:38 PMPPASS
Final walkthrough passed. Fire sprinkler permit finaled.
FIR14-00372 INSP-Alarm Testing8/31/20149/3/20149/3/2014 3:54:49 PMANR
Completed initial project walkthrough. Items noted include; adjust notification at locations marked on plans at the 3rd, 2nd and 1st floors, (cd settings, spacing, height AFF), provide WP device at a 2nd floor bathroom, relocate a/v at the 2nd floor TV room, provide SD at the 2nd floor NAC, monitor sprinkler tamper at the 1st floor elevator control, relocate a/v at the kitchen exit access, post signage at the door to the FACP room, provide lock at circut breaker, post points map per review comments, provide documents cabinet. Provide plan modification for resubmittal to reflect field changes such as deleted ID's, door mag relays, elevator hat, changed room uses, added 1st floor vestibule, new ceiling mount devices in place of wall mount, - include IP DACT in place of phone lines. Remove all non-functional devices and system components from the previous panel including MP, SD, HD, power supplies, etc. prior to final.
FIR14-00576 INSP-Final Inspection9/3/20149/3/20149/3/2014 3:37:08 PMPPASS
Noted correction and functional testing completed. Fire alarm permit finaled.
BLD14-01907 FIRE-Final Inspection9/2/20149/3/20149/3/2014 11:56:40 AMAPASS
Fire life safety finaled.
FIR14-00601 INSP-Final Inspection9/3/20149/3/20149/3/2014 11:55:41 AMPPASS
Fire sprinkler work passed walkthrough. Permit finaled.
FIR14-00261 INSP-Sprinkler Rough-in/Hydro9/2/20149/3/20149/3/2014 11:54:07 AMAPART
OH hydrostatic testing for the 1st thru 4th floors including the standpipe completed acceptable.
BLD14-01951 FIRE-Final Inspection9/2/20149/3/20149/3/2014 10:19:36 AMAFAIL
Modifications to existing fire sprinkler coverage will be necessary due to remodel work. Remainder of life safety items appear satisfactory.