Inspections for the day of: Thursday, September 4, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00289 INSP-Sprinkler Rough-in/Hydro9/4/20089/4/20089/4/2008 5:47:41 PMANR
Site visit confirmed repairs for leakage at overhead piping are not yet complete for re-test.
BLD08-01358 FIRE-Conference9/4/20089/4/20089/4/2008 5:46:29 PMADONE
On site visit, regarding door hardware completion.
FIR08-00387 FIR-Aging Inspection9/4/20089/4/20089/4/2008 5:42:08 PM DEFR
Pending site inspection request.
FIR08-00424 INSP-Sprinkler Rough-in/Hydro9/4/20089/4/20089/4/2008 5:38:18 PMPDEFR
Intended for project related permit #FIR08-00289.
BLD07-03215 FIRE-Final Inspection9/4/20089/4/20089/4/2008 5:35:30 PMPNR
Work in progress, not ready for final inspection at this time.
BLD08-01053 FIRE-Final Inspection9/3/20089/4/20089/4/2008 5:32:29 PMAPASS
Items on C/N verified for completion, life safety passed.
FIR08-00164 INSP-Sprinkler Rough-in/Hydro9/4/20089/4/20089/4/2008 5:29:00 PMAPART
Repairs completed, UG fire supply line hydrostatic testing passed. Noted missing sprinkler piping and head coverage at the electrical room adjacent to the riser, also noted FDC is over max. 4' above grade due to finish slope-see fire code review notes item #51 for FDC requirements. Overhead install not inspected to date.