MEC18-02283
| Rough-in | 5/22/2018 | 5/23/2018 | 5/23/2018 1:25:12 PM | P | PART |
|
|
elevator shaft Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover mechanical shaft behind elevator on 1st, and 2nd floor
|
MEC17-01976
| Final | 5/22/2018 | 5/23/2018 | 5/23/2018 10:55:45 AM | A | PART |
|
|
Whole Bldg please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Temporary occupancy okay. Missing return/transfer ducts and grills in office area, missing condensate p-trap on rtu
|
MEC18-02150
| Rough-in | 5/22/2018 | 5/23/2018 | 5/23/2018 10:02:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Stegemann
|
MEC18-01888
| Final | 5/22/2018 | 5/23/2018 | 5/23/2018 9:19:40 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Mendiola - Gas meter is undersized for the btu load
|
MEC17-04433
| Rough-in | 5/22/2018 | 5/23/2018 | 5/23/2018 9:02:19 AM | A | FAIL |
|
|
early am- Travis Phone #: ###-#### - Grease duct light test fail. Need to weld up holes in grease duct, need 3" cleear space around grease duct for fire wrap, need 18" clearance to combustables above hood
|
MEC18-02283
| Rough-in | 5/22/2018 | 5/23/2018 | 5/22/2018 2:37:31 PM | A | CANC |
|
|
elevator shaft Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|