Inspections for the day of: Friday, June 22, 2018.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01251 Final6/21/20186/22/20186/22/2018 4:11:18 PMPFAIL
Final - call David Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Need drip legs on gas piping for furnace and water heater
MEC18-02924 Pressure Test6/21/20186/22/20186/22/2018 3:28:42 PMPPASS
Phone #: ###-#### Inspection requested via web by Angie Thome - 20lb gas pass
MEC18-02924 Rough-in6/21/20186/22/20186/22/2018 3:28:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Angie Thome -
1) Need approved manual J onsite
2) Fresh air duct can not come from the roof
3) Need a minimum of 4" wide framing on wall with dryer duct so duct isn't smashed
4) Missing nail plates on dryer duct
MEC18-02927 Rough-in6/22/20186/22/20186/22/2018 3:05:56 PMPFAIL
Phone #: ###-#### Inspection requested via web by Bryan Palmer - Bathroom exhaust not installed per approved plans, need 1" clearance from combustables on b-vent for water heater, Need to support spiral duct work in between joists on the mezzanine in a approved manor.
MEC18-02927 Pressure Test6/22/20186/22/20186/22/2018 3:04:02 PMPPASS
Phone #: ###-#### Inspection requested via web by Bryan Palmer - 20lb gas pass on piping to water heater
MEC18-02272 Rough-in6/21/20186/22/20186/22/2018 3:04:02 PMPPASS
Rough-in inspection of main corridor, side corridor, woman''s bathroom, and mother''s bathrooms duct work. John Brunnet will be the site contact. Please call 30 minutes prior to arriving on site. ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical - okay to cover
MEC18-02921 Final6/21/20186/22/20186/22/2018 3:04:02 PMPNR
Contact: Bob Snow Phone #: ###-#### Inspection requested via web by RM Mechanical
MEC18-02283 Rough-in6/22/20186/22/20186/22/2018 2:25:33 PMPFAIL
Rough in on the fourth floor only Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Need to complete installation of line sets in walls
MEC18-00928 Final6/22/20186/22/20186/22/2018 1:11:55 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak - Need approved supports on PVC flue, and gas piping, need combustion air for mechanical room
MEC18-02926 Final6/22/20186/22/20186/22/2018 11:43:31 AMPPASS
We will have all correction taken care of, I will drop by around 11:00 and verify also. Inspection requested via web by Floyd Floyd Peek
MEC18-01466 Final6/22/20186/22/20186/22/2018 11:01:48 AMPPASS
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak
MEC18-02742 Final6/22/20186/22/20186/22/2018 10:41:17 AMPPASS
extended plumbing vent to 37" above RTU. Strapped gas line in 3 places. Call ahead and I will meet you there. Thank you Phone #: ###-#### Inspection requested via web by jeremy wanders
MEC18-02853 Final6/21/20186/22/20186/22/2018 10:15:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC18-02669 Final6/18/20186/22/20186/22/2018 9:58:47 AMAPASS
Please call when you are on the way so we can make sure someone is there Phone #: ###-#### Inspection requested via web by Dan McFate
MEC18-02213 Final6/15/20186/22/20186/22/2018 9:37:41 AMAPASS
Call customer in route Clive Strong ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout
MEC18-02477 Rough-in6/20/20186/22/20186/22/2018 9:11:27 AMAPART
Please call Cody when inspector is headed that way. Thank you Phone #: ###-#### Inspection requested via web by Nick Drake Okay to sheetrock hard lids. There is more ductwork to be run once ceilings have been sheetrocked
MEC17-04450 Final6/21/20186/22/20186/22/2018 9:09:07 AMAPASS
I thought this had been requested last November. Robin Phone #: ###-#### Inspection requested via web by Robin Cox
MEC17-01833 Mec-Aging Inspection6/22/20186/22/20186/22/2018 6:38:29 AM DONE
Expired
MEC17-01833 DOC - Permit Expired6/22/20186/22/20186/22/2018 6:38:14 AMAPASS
MEC17-04528 Mec-Aging Inspection6/22/20186/22/20186/22/2018 6:37:46 AM CANC
MEC17-04545 Mec-Aging Inspection6/22/20186/22/20186/22/2018 6:37:07 AM CANC
MEC17-03168 Mec-Aging Inspection6/22/20186/22/20186/22/2018 6:36:17 AM CANC
MEC17-04543 Mec-Aging Inspection6/22/20186/22/20186/22/2018 6:36:06 AM CANC