Inspections for the day of: Thursday, July 12, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-04433 Final7/11/20187/12/20187/12/2018 1:31:43 PMAFAIL
John Phone #: ###-####
1) Need to seal return duct in kitchen
2) Need to complete fire wrap on grease duct ( needs to be done by a certified individual).
3) Grease drain needs to be ran in Black iron, stainless steel, or copper.
4) Need to complete vent terminations on outside of building
5) Pool heater vents need to be installed per manufactures instructions.
6) Need to support duct at canvas connector on dehumidification unit.
7) Need final air balance report
8) Need to install intake hood on MAU for 1st floor
9) Need to protect insulation on outside duct for MAU 1st floor
MEC18-03349 Pressure Test7/12/20187/12/20187/12/2018 12:43:02 PMPCANC
please call our lead installer Brad when 30 mins in route. End of day would be preferred, 3-5p if possible. Phone #: ###-#### >> Inspection requested via web by Rick Montgomery Inspection cancelled from web by: Rick Montgomery
MEC18-02944 Rough-in7/12/20187/12/20187/12/2018 11:30:39 AMAPASS
MEC18-01895 Rough-in7/11/20187/12/20187/12/2018 11:30:21 AMAPART
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth - Okay to insulate supply duct in 2nd, and 3rd floor bathrooms
MEC18-02283 Rough-in7/11/20187/12/20187/12/2018 11:30:21 AMAPART
5th floor cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lid drop ceilings in units 502, 503, 504, 505, 506, 507, 508, 510, 511, 517, 519. Okay to cover bottom of TGI's and walls in unit 314