Inspections for the day of: Monday, July 16, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03411 Pressure Test7/16/20187/16/20187/16/2018 4:32:20 PMPPART
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Gas pressure test fail, 5lb flue pass on both furnaces
MEC18-03411 Rough-in7/16/20187/16/20187/16/2018 4:31:33 PMPFAIL
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN -
1) Need approved manual J onsite
2) Exhaust fan not connected
3) Need to seal floor boots to floor
4) Missing nail plates on linesets, and dryer ducts
5) Missing fresh air to return plenum
MEC17-04433 Final7/16/20187/16/20187/16/2018 3:37:24 PMPPART
John Phone #: ###-#### - Phase 2 temporary occupancy okay. Need final air balance report still
MEC18-02283 Rough-in7/16/20187/16/20187/16/2018 2:50:42 PMPPASS
2nd floor cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover walls, & TGI's on 2nd floor
MEC18-03355 Rough-in7/15/20187/16/20187/16/2018 2:34:47 PMPPASS
Ceiling cover Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - okay to cover ceilings in space 427