MEC18-03411
| Pressure Test | 7/16/2018 | 7/16/2018 | 7/16/2018 4:32:20 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Gas pressure test fail, 5lb flue pass on both furnaces
|
MEC18-03411
| Rough-in | 7/16/2018 | 7/16/2018 | 7/16/2018 4:31:33 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 1) Need approved manual J onsite 2) Exhaust fan not connected 3) Need to seal floor boots to floor 4) Missing nail plates on linesets, and dryer ducts 5) Missing fresh air to return plenum
|
MEC17-04433
| Final | 7/16/2018 | 7/16/2018 | 7/16/2018 3:37:24 PM | P | PART |
|
|
John Phone #: ###-#### - Phase 2 temporary occupancy okay. Need final air balance report still
|
MEC18-02283
| Rough-in | 7/16/2018 | 7/16/2018 | 7/16/2018 2:50:42 PM | P | PASS |
|
|
2nd floor cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover walls, & TGI's on 2nd floor
|
MEC18-03355
| Rough-in | 7/15/2018 | 7/16/2018 | 7/16/2018 2:34:47 PM | P | PASS |
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - okay to cover ceilings in space 427
|