Inspections for the day of: Friday, June 5, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01413 Final6/4/20206/5/20206/5/2020 3:43:08 PMPPASS
Please call prior to heading out ###-####. Please give 30 heads up. Would prefer closer to 4. Phone #: ###-#### Inspection requested via web by Ashley Van Cleave
MEC20-02166 Final6/4/20206/5/20206/5/2020 3:42:58 PMPPASS
Call ahead to Michael @ ###-#### when headed to the residence Phone #: ###-#### Inspection requested via web by Sarah Small
MEC20-02167 Final6/2/20206/5/20206/5/2020 3:38:35 PMPPASS
INSTALLER AL ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC20-02089 Rough-in6/5/20206/5/20206/5/2020 3:01:04 PMPPASS
Cover Inspection
Please contact John Shartzer prior to arrival Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- above hard lids 1st floor okay
MEC20-02052 Pressure Test6/5/20206/5/20206/5/2020 2:46:58 PMPCANC
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- schedualed by mistake
MEC19-04496 Final6/4/20206/5/20206/5/2020 1:43:13 PMPFAIL
Can you call Garrit at ###-#### before you go. He will need to be there to let you in. Phone #: ###-#### Inspection requested via web by Kristy Newkirk
- please add new erv to permit, I dont need to go back,
- reschedual and ill pass it
MEC19-00377 Mec-Aging Inspection6/5/20206/5/20206/5/2020 11:00:18 AM CANC
wip
MEC20-01851 Final6/4/20206/5/20206/5/2020 10:42:20 AMAFAIL
Homeowner George Rogers ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- condencer needs locking caps
- send picture for re-inspection
MEC20-02090 Rough-in6/4/20206/5/20206/5/2020 10:21:47 AMAFAIL
Please contact GM Jordan if any questions arise at the job site. Phone #: ###-#### Inspection requested via web by Ashley Van Cleave
- range duct rough-in not complete
- manual j shows pantry with a supply and return please revise manual j
- there is a open supply run in the crawl
MEC20-01904 Rough-in6/4/20206/5/20206/5/2020 9:48:05 AMAFAIL
Garage Code: 3517 - Builder: ###-#### - HVAC: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- flue tests in basement at zero
- fresh air 2nd floor to return plenum, not return can in master closet, that return not shown on manual j
MEC20-01904 Pressure Test6/4/20206/5/20206/5/2020 9:45:35 AMAPASS
Garage Code: 3517 - Builder: ###-#### - HVAC: ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
-60lb,
- 5lb 2nd floor
MEC19-05384 Rough-in6/4/20206/5/20206/5/2020 9:17:58 AMAPASS
flue test Phone #: ###-#### Inspection requested via web by Brandon Sorensen
-5lb x8