Inspections for the day of: Tuesday, January 14, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00718 INSP-Final Inspection1/14/20201/14/20201/14/2020 3:08:52 PMPCANC
Not ready.

Call James about repair work around access panel Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00221 INSP-Sprinkler Rough-in/Hydro1/13/20201/14/20201/14/2020 1:38:49 PMPPASS
1st floor overhead piping hydro test witnessed with no pressure loss (North and South Buildings)

Please contact Tom Smalls for inspection time. This inspection is for 1st floor and parking garage. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR20-00001 INSP-Sprinkler Rough-in1/13/20201/14/20201/14/2020 10:55:17 AMAPASS
Rough in passed all piping okay for cover.




Austin Farnworth is the contact for this RTC inspection. He is requesting notice 30 min before appointment as he will be at another job site. Thank you so much for your help. Have a great day. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-04991 FIRE-Final Inspection1/13/20201/14/20201/14/2020 10:05:25 AMAFAIL

Post occupant load sign, repair exit discharge lights and repair emergency lights. Type 1 hood suppression system current with inspection.


memo Phone #: ###-####
FIR19-00754 INSP-Sprinkler Rough-in1/14/20201/14/20201/14/2020 9:41:15 AMPPART
Need all small documents prior to next inspection. Plan mods needed showing additional fittings in main piping, riser nipple lengths and pipe size changes. Upright sprinkler heads appear to obstructed in the low roof portioin of project. Need to meet three times rule. General rough in looks okay.

George Jess is the contact for this RTC Inspection. Thank you for your help and have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00662 INSP-Sprinkler Rough-in1/13/20201/14/20201/14/2020 9:34:23 AMACANC
Wrong permit scheduled.


George Jess is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus