FIR19-00230
| INSP-Alarm Testing | 1/15/2020 | 1/16/2020 | 1/17/2020 10:16:12 AM | A | DONE |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
Tested duct detection and fire smoke dampers, elevator recall and shunt, basement thru floor 3 wet sprinklers in stair L, sprinkler bell, manual alarm. All operated properly. Strobes need to be installed in the trash rooms. Centeral station monitoring was not verified and some sprinkler work still needs to be verified. LGM
|
FIR19-00221
| INSP-Sprinkler Rough-in/Hydro | 1/16/2020 | 1/16/2020 | 1/16/2020 3:41:54 PM | P | PASS |
|
|
The forward flush passed. Please contact Rick Fry for time of inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR19-00775
| INSP-Sprinkler Rough-in/Hydro | 1/15/2020 | 1/16/2020 | 1/16/2020 3:41:24 PM | P | PASS |
|
|
Underground supply piping hydro test witnessed.
bld K // Kyle Phone #: ###-####
|
FIR19-00776
| INSP-Sprinkler Rough-in/Hydro | 1/15/2020 | 1/16/2020 | 1/16/2020 3:41:02 PM | P | PASS |
|
|
Underground supply piping hydro test witnessed.
bld L // Kyle Phone #: ###-####
|
FIR19-00773
| INSP-Sprinkler Rough-in/Hydro | 1/15/2020 | 1/16/2020 | 1/16/2020 3:40:33 PM | P | PASS |
|
|
Underground supply piping hydro test witnessed.
bld A // Kyle Phone #: ###-####
|
FIR19-00774
| INSP-Sprinkler Rough-in/Hydro | 1/15/2020 | 1/16/2020 | 1/16/2020 3:39:51 PM | P | FAIL |
|
|
Underground supply line hydro failed due to visible loss of pressure on the guage.
bld B // Kyle Phone #: ###-####
|
BLD19-01949
| FIRE-Conference | 1/16/2020 | 1/16/2020 | 1/16/2020 1:27:45 PM | P | DONE |
|
|
The phone conferenced with the geal contractor about the possible need for a sprinkler contractor to to determine whether sprinkler coverage is needed in the new construction areas.
|
FIR20-00007
| INSP-Final Inspection | 1/16/2020 | 1/16/2020 | 1/16/2020 1:21:31 PM | P | PASS |
|
|
Permit finaled. Tony Phone #: ###-####
|
FIR19-00790
| INSP-Sprinkler Rough-in | 1/15/2020 | 1/16/2020 | 1/16/2020 12:54:51 PM | A | PASS |
|
|
The underground supply line is ok for cover from the point of connection to the IBR. The IBR has not been installed yet and will require another inspection.
cover // Kyle Phone #: ###-####
|
FIR19-00791
| INSP-Sprinkler Rough-in | 1/15/2020 | 1/16/2020 | 1/16/2020 12:54:31 PM | A | PASS |
|
|
The underground supply line is ok for cover from the point of connection to the IBR. The IBR has not been installed yet and will require another inspection.
cover // Kyle Phone #: ###-####
|
BLD19-04186
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 10:22:32 AM | A | PASS |
|
|
Life safety passed.
Suman Phone #: ###-####
|
BLD19-04949
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 10:20:20 AM | A | PASS |
|
|
Life safety passed. Brian Phone #: ###-####
|
BLD19-04950
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 10:19:27 AM | A | PASS |
|
|
Life safety passed.
Brian Phone #: ###-####
|
BLD19-03234
| FIRE-Final Inspection | 1/15/2020 | 1/16/2020 | 1/16/2020 9:40:54 AM | A | FAIL |
|
|
Fire life safety wil be ok to sign off when the project related fire alarm permit is finaled.
Troy,
Here is my final fire.
Thanks,
Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|
FIR18-00358
| INSP-Alarm Testing | 1/15/2020 | 1/16/2020 | 1/15/2020 2:13:26 PM | A | CANC |
|
|
Call Jake Adams. District and Alarm Co personnel will be on site. Phone #: ###-#### >> Inspection requested via web by Jeff Gooch Inspection cancelled from web by: Jeff Gooch
|