Inspections for the day of: Thursday, January 16, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00230 INSP-Alarm Testing1/15/20201/16/20201/17/2020 10:16:12 AMADONE
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price

Tested duct detection and fire smoke dampers, elevator recall and shunt, basement thru floor 3 wet sprinklers in stair L, sprinkler bell, manual alarm. All operated properly. Strobes need to be installed in the trash rooms. Centeral station monitoring was not verified and some sprinkler work still needs to be verified. LGM
FIR19-00221 INSP-Sprinkler Rough-in/Hydro1/16/20201/16/20201/16/2020 3:41:54 PMPPASS
The forward flush passed. Please contact Rick Fry for time of inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR19-00775 INSP-Sprinkler Rough-in/Hydro1/15/20201/16/20201/16/2020 3:41:24 PMPPASS
Underground supply piping hydro test witnessed.

bld K // Kyle Phone #: ###-####
FIR19-00776 INSP-Sprinkler Rough-in/Hydro1/15/20201/16/20201/16/2020 3:41:02 PMPPASS
Underground supply piping hydro test witnessed.

bld L // Kyle Phone #: ###-####
FIR19-00773 INSP-Sprinkler Rough-in/Hydro1/15/20201/16/20201/16/2020 3:40:33 PMPPASS
Underground supply piping hydro test witnessed.

bld A // Kyle Phone #: ###-####
FIR19-00774 INSP-Sprinkler Rough-in/Hydro1/15/20201/16/20201/16/2020 3:39:51 PMPFAIL
Underground supply line hydro failed due to visible loss of pressure on the guage.

bld B // Kyle Phone #: ###-####
BLD19-01949 FIRE-Conference1/16/20201/16/20201/16/2020 1:27:45 PMPDONE
The phone conferenced with the geal contractor about the possible need for a sprinkler contractor to to determine whether sprinkler coverage is needed in the new construction areas.
FIR20-00007 INSP-Final Inspection1/16/20201/16/20201/16/2020 1:21:31 PMPPASS
Permit finaled. Tony Phone #: ###-####
FIR19-00790 INSP-Sprinkler Rough-in1/15/20201/16/20201/16/2020 12:54:51 PMAPASS
The underground supply line is ok for cover from the point of connection to the IBR. The IBR has not been installed yet and will require another inspection.

cover // Kyle Phone #: ###-####
FIR19-00791 INSP-Sprinkler Rough-in1/15/20201/16/20201/16/2020 12:54:31 PMAPASS
The underground supply line is ok for cover from the point of connection to the IBR. The IBR has not been installed yet and will require another inspection.

cover // Kyle Phone #: ###-####
BLD19-04186 FIRE-Final Inspection1/15/20201/16/20201/16/2020 10:22:32 AMAPASS
Life safety passed.

Suman Phone #: ###-####
BLD19-04949 FIRE-Final Inspection1/15/20201/16/20201/16/2020 10:20:20 AMAPASS
Life safety passed. Brian Phone #: ###-####
BLD19-04950 FIRE-Final Inspection1/15/20201/16/20201/16/2020 10:19:27 AMAPASS
Life safety passed.

Brian Phone #: ###-####
BLD19-03234 FIRE-Final Inspection1/15/20201/16/20201/16/2020 9:40:54 AMAFAIL
Fire life safety wil be ok to sign off when the project related fire alarm permit is finaled.

Troy,

Here is my final fire.

Thanks,

Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
FIR18-00358 INSP-Alarm Testing1/15/20201/16/20201/15/2020 2:13:26 PMACANC
Call Jake Adams. District and Alarm Co personnel will be on site. Phone #: ###-#### >> Inspection requested via web by Jeff Gooch Inspection cancelled from web by: Jeff Gooch