Inspections for the day of: Thursday, January 17, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00741 INSP-Sprinkler Rough-in/Hydro1/17/20131/17/20131/17/2013 4:15:50 PMPPASS
Overhead hydro and rough-in passed.
FIR12-00557 INSP-Final Inspection1/17/20131/17/20131/17/2013 3:59:58 PMPPASS
Permit finaled
BLD12-00334 FIRE-Final Inspection1/17/20131/17/20131/17/2013 3:11:05 PMPFAIL
The project related fire alarm permit needs addressed and then life safety can be finaled.
BLD12-00342 FIRE-Final Inspection1/17/20131/17/20131/17/2013 3:09:50 PMPFAIL
The project related fire alarm permit needs addressed, correct fire extinguishers as discussed and the NFPA signs posted.
BLD12-00344 FIRE-Final Inspection1/17/20131/17/20131/17/2013 2:50:47 PMPPASS
Life safety passed
BLD12-00220 FIRE-Final Inspection1/17/20131/17/20131/17/2013 2:37:23 PMPPASS
life safety passed
BLD12-00081 FIRE-Final Inspection1/17/20131/17/20131/17/2013 2:28:18 PMPPASS
Life safety passed
FIR09-00510 INSP-Conference1/17/20131/17/20131/17/2013 2:09:14 PMPDONE
Went over details to final this project with Matt Casey. and with the onsite store manager Alan. It appears plan modifications will be required.
BLD12-02304 FIRE-Final Inspection1/17/20131/17/20131/17/2013 1:56:23 PMPPASS
Life safety passed
FIR12-00744 INSP-Final Inspection1/16/20131/17/20131/17/2013 1:45:27 PMPFAIL
The audible notification devices are not synchronized as required per NFPA 72 18.4.2.5 . The tenant area new devices do not sync with the existing area corridor devices.
FIR12-00741 INSP-Sprinkler Rough-in/Hydro1/17/20131/17/20131/17/2013 11:13:43 AMPFAIL
Overhead hydro test for the new storage area piping failed due to visable drop on the pressure guage. Also the earthquake attachments do not match the city approved drawings and don't have through bolts for the wood members per NFPA 13 Chapter 9.