Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02322 FIRE-Conference1/17/20201/17/20201/17/2020 3:55:58 PMPDONE
I verified functionality of the basement, second and third floor exit signs and emergency lights. First floor was not ready. I noted a missing exit sign at the center basement stairs. Fire extinguishers are in place except for one that is missing. Door hardware appears ok. This inspection was for the north building and the associated exit paths only. Building B is not ready yet. The exit signs/emergency lights/fire extinguishers and door hardware are the only items inspected today. The fire alarm and fire sprinkler permits stil need addressed. I spoke to plan review about note 35 on the life safety comments and will need to follow up. Emergency evac plan needs to be addressed as well.
FIR19-00790 INSP-Sprinkler Rough-in1/17/20201/17/20201/17/2020 1:49:43 PMPPASS
The remaining underground supply piping is ok for cover.
Kile Phone #: ###-####
FIR19-00791 INSP-Sprinkler Rough-in1/17/20201/17/20201/17/2020 1:49:24 PMPPASS
The remaining underground supply piping is ok for cover.

Kile Phone #: ###-####
NAF19-00068 INSP-Sprinkler Rough-in/Hydro1/17/20201/17/20201/17/2020 1:48:49 PMPPASS
Overhead hydro witnessed.

This inspection is for an overhead hydro. Please contact Troy Nelson for an inspection time. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR19-00221 INSP-Final Inspection1/16/20201/17/20201/17/2020 1:47:20 PMAFAIL
For a final the test papers are needed and the canopies installed (need rock work) on the exterior dry sidewall sprinkler heads. Also the Life Safety Plan review Comments, note 35, state that Class 1 stand pipes are required. I have a call into plan review to verify an exception has been met.

Please contact Tom Smalls for a final inspection. Phone #: ###-#### Inspection requested via web by Daniel Buccino
FIR19-00230 INSP-Alarm Testing1/16/20201/17/20201/17/2020 1:41:16 PMADONE
For a final sign off as-builts are needed to be approved and the building shall report out to the monitoring company with the building address for these signals.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR19-00909 INSP-Final Inspection1/15/20201/17/20201/17/2020 9:23:05 AMAFAIL
Need the smoke detector locations to match the approved plans. No testing performed.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00679 INSP-Final Inspection1/15/20201/17/20201/16/2020 3:39:49 PMACANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball