FIR18-00827
| INSP-Sprinkler Rough-in | 1/23/2019 | 1/24/2019 | 1/25/2019 11:01:32 AM | A | PART |
|
|
Third floor tenting and rough-in passed. Piping can be covered. First and second floors not looked at due to time constraints.The piping in the breezways can not be covered until heat tape is verified.
Gerarrdo is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00455
| INSP-Alarm Testing | 1/23/2019 | 1/24/2019 | 1/25/2019 9:06:53 AM | P | DONE |
|
|
Lee witnessed testing of the audio/visuals and smoke dampers.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
FIR18-00849
| INSP-Sprinkler Rough-in/Hydro | 1/24/2019 | 1/24/2019 | 1/24/2019 3:40:56 PM | P | PASS |
|
|
The overhead hydro test and forward flush passed
|
FIR18-00510
| INSP-Sprinkler Rough-in | 1/24/2019 | 1/24/2019 | 1/24/2019 3:29:12 PM | P | CANC |
|
|
Rescheduled for tomorrow morning.
Third floor rough in. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00901
| INSP-Sprinkler Rough-in | 1/24/2019 | 1/24/2019 | 1/24/2019 2:52:06 PM | P | PASS |
|
|
Hanger attachments are ok for cover.
Mike Phone #: ###-####
|
FIR18-00961
| INSP-Final Inspection | 1/21/2019 | 1/24/2019 | 1/24/2019 2:50:45 PM | A | FAIL |
|
|
Permit will be ok to final when plan review approved the as-builts.
Please call Nate roughly 20 minutes prior to inspection. Nate can be reached at ###-#### Phone #: ###-#### Inspection requested via web by jason petty
|
BLD19-00179
| FIRE-Final Inspection | 1/18/2019 | 1/24/2019 | 1/24/2019 2:25:15 PM | P | PASS |
|
|
Life safety passed. Owner needs to provide single action hardware prior to a building inspection as discussed.
CAll ahead // Ann Phone #: ###-####
|
FIR18-00308
| INSP-Final Inspection | 1/22/2019 | 1/24/2019 | 1/24/2019 1:47:43 PM | P | PASS |
|
|
permit finaled
Tony Phone #: ###-####
|
FIR18-00708
| INSP-Final Inspection | 1/22/2019 | 1/24/2019 | 1/24/2019 1:47:21 PM | P | PASS |
|
|
permit finaled
Tony Phone #: ###-####
|
FIR18-00428
| INSP-Final Inspection | 1/22/2019 | 1/24/2019 | 1/24/2019 1:46:51 PM | P | PASS |
|
|
Permit finaled
Tony Phone #: ###-####
|
BLD18-03410
| FIRE-Final Inspection | 1/23/2019 | 1/24/2019 | 1/24/2019 11:56:10 AM | A | PASS |
|
|
life safety passed
Stan Phone #: ###-####
|
BLD19-00061
| FIRE-Final Inspection | 1/23/2019 | 1/24/2019 | 1/24/2019 11:32:35 AM | A | PASS |
|
|
life safety passed
Matt Phone #: ###-####
|
NAF19-00001
| INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/24/2019 | 1/24/2019 10:35:13 AM | A | FAIL |
|
|
No testing performed. Verification is needed that the Ansul suppression system is approved by Ansul to be installed, as is, in the Gaylord water wash hood.
Call prior to going Phone #: 2086317804 >> Inspection requested via mobile web by Nate
|
NAF19-00002
| INSP-Final | 1/23/2019 | 1/24/2019 | 1/24/2019 10:34:06 AM | A | DONE |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR18-00614
| INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/24/2019 | 1/24/2019 10:32:38 AM | A | PASS |
|
|
Underground supply hydro test passed.
Troy Nelson will call when ready for UG Hyrdo Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR19-00021
| INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/24/2019 | 1/24/2019 10:11:41 AM | A | CANC |
|
|
Call Alicia before heading out. Should be ready by 8am. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00965
| INSP-Sprinkler Rough-in | 1/23/2019 | 1/24/2019 | 1/24/2019 8:56:34 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
Kerri Phone #: ###-####
|
FIR19-00028
| INSP-Final Inspection | 1/23/2019 | 1/24/2019 | 1/24/2019 8:08:15 AM | A | CANC |
|
|
As early as possible Phone #: 2085905075 >> Inspection requested via mobile web by Barney Inspection cancelled via mobile web on Thursday, January 24, 2019.
|
FIR18-00941
| INSP-Final Inspection | 1/22/2019 | 1/24/2019 | 1/24/2019 7:48:29 AM | A | FAIL |
|
|
No city approved plans on site. The notification devices as pointed out to me in the scope of work did function.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00642
| INSP-Final Inspection | 1/21/2019 | 1/24/2019 | 1/24/2019 12:00:00 AM | A | DONE |
|
|
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.
3:30 pm test is too late for Target. Nathan cancelled.
|