BLD18-00084
| FIRE-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 3:34:05 PM | P | FAIL |
|
|
Provide/repair the exit signs and emergency lights as per the approved plans and discussion. Provide single action hardware as discussed. no plumbing permit pulled yet
|
BLD17-02141
| FIRE-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 3:29:31 PM | P | CANC |
|
|
Canceled due to time constraints
Rod Phone #: ###-####
|
FIR17-00748
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:28:45 PM | P | CANC |
|
|
Call Anthony to coordinate time. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-03830
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:20:03 PM | A | CANC |
|
|
Need the project related hood suppression permit and fire alarm permit finaled prior to a life safety inspection. I was willing to perform a conference for the life safety but due to time constraints and prior obligations was unable to.
Jade Phone #: ###-####
|
BLD17-03975
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:03:56 PM | A | FAIL |
|
|
Provide single action hardware on the interior door with ability to unlock from outside, remove the thumb turn deadbolt from the north exit door, mount the fire extinguisher, provide smoke alarms/carbon monoxide detectors as per the approved plans, provid ecode compliant exit signs/emergency lights/exit discharge lights as per the plans and fire review notes, provide covers for the electrical outlets.
|
BLD17-03674
| FIRE-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 2:16:54 PM | P | PASS |
|
|
life safety passed
Mike ###-####
|
FIR17-00352
| INSP-Sprinkler Rough-in/Hydro | 1/25/2018 | 1/26/2018 | 1/26/2018 2:15:57 PM | P | PASS |
|
|
Overhead hydro test passed
|
FIR18-00050
| INSP-Sprinkler Rough-in | 1/25/2018 | 1/26/2018 | 1/26/2018 1:57:03 PM | P | CANC |
|
|
Call Anthony to coordinate time. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR18-00010
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 1:09:27 PM | A | FAIL |
|
|
Provide modification to the two strobes to provide coverage as discussed and marked on the plans. Provide proper placement of the duct smoke detectors as discussed and provide testing. The hood suppression system reported as alarm to the FACP but the alarm signals did not report off site. Provide as-builts of changes prior to a final sign off.
Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR18-00034
| INSP-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 1:06:26 PM | P | FAIL |
|
|
Need plans and documents and the closeout documents. I witnessed the puff test and it functioned correctly and reported to the panel but did not report off site.
Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR17-00773
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 12:56:39 PM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00047
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 11:50:34 AM | A | FAIL |
|
|
Not ready for a final. Inspection was for a rough-in. The additional sprinkler coverage in the fire place is ok for cover and the two pendants have been relocated further from the soffits.
call before to meet // Roy Phone #: ###-####
|
FIR17-00630
| INSP-Final Inspection | 1/24/2018 | 1/26/2018 | 1/26/2018 11:15:37 AM | A | FAIL |
|
|
Contact the plan reviewer for guidance on wether a plan modification is needed or if as-builts will suffice.The one line riser does not match actual points and descriptions such as dry system pressure switch, AES instead of phone lines....ect. Also per dicussion with on site electrician, hvac and general contractor not all of the duct smoke detectors are functional I stated that all devices, as shown on the plans, need to be installed/cunctional/tested or plans will need to be modified to delete the devices. The deleted devices will require a separate permit when installed prior to an occupancy approval for the individual tenants. Today we tested all devices except the flow switch for system #2 and the duct smoke detectors.
This is for Belmont Core Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR17-00686
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:32:29 AM | A | PASS |
|
|
permit finaled
|
FIR17-00631
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:31:49 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00593
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:31:07 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00687
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:30:13 AM | A | FAIL |
|
|
This permit can be finaled when the flow switch for the sprinkler riser that serves this tenant space has been tested. It currently has no inspectors test for testing of the new flow switch
|
BLD16-04309
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:28:34 AM | P | PASS |
|
|
life safety passed
Phone #: ###-#### Inspection requested via web by David Scaggs
|
FIR17-00353
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:27:58 AM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-04588
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:04:38 AM | A | PASS |
|
|
Life safety passed
Spence Phone #: ###-####
|
BLD16-02806
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 8:34:52 AM | A | FAIL |
|
|
Provide address, provide permanant exit discharge lighting, mount the occupant load sign, provide testing of the duct smoke detectors.
Phone #: ###-#### Inspection requested via web by Ryan Wilhelm
|
FIR17-00707
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 8:33:51 AM | A | PASS |
|
|
The hood suppression system shut down the electrical. Permit finaled
Dave Phone #: ###-####
|
FIR18-00056
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 8:22:52 AM | A | PART |
|
|
Rough-in passed. piping is ok to cover. Not ready for final yet.
|