Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00084 FIRE-Final Inspection1/26/20181/26/20181/26/2018 3:34:05 PMPFAIL
Provide/repair the exit signs and emergency lights as per the approved plans and discussion. Provide single action hardware as discussed. no plumbing permit pulled yet
BLD17-02141 FIRE-Final Inspection1/26/20181/26/20181/26/2018 3:29:31 PMPCANC
Canceled due to time constraints

Rod Phone #: ###-####
FIR17-00748 INSP-Final Inspection1/25/20181/26/20181/26/2018 3:28:45 PMPCANC
Call Anthony to coordinate time. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD17-03830 FIRE-Final Inspection1/25/20181/26/20181/26/2018 3:20:03 PMACANC
Need the project related hood suppression permit and fire alarm permit finaled prior to a life safety inspection. I was willing to perform a conference for the life safety but due to time constraints and prior obligations was unable to.

Jade Phone #: ###-####
BLD17-03975 FIRE-Final Inspection1/25/20181/26/20181/26/2018 3:03:56 PMAFAIL
Provide single action hardware on the interior door with ability to unlock from outside, remove the thumb turn deadbolt from the north exit door, mount the fire extinguisher, provide smoke alarms/carbon monoxide detectors as per the approved plans, provid ecode compliant exit signs/emergency lights/exit discharge lights as per the plans and fire review notes, provide covers for the electrical outlets.
BLD17-03674 FIRE-Final Inspection1/26/20181/26/20181/26/2018 2:16:54 PMPPASS
life safety passed

Mike ###-####
FIR17-00352 INSP-Sprinkler Rough-in/Hydro1/25/20181/26/20181/26/2018 2:15:57 PMPPASS
Overhead hydro test passed
FIR18-00050 INSP-Sprinkler Rough-in1/25/20181/26/20181/26/2018 1:57:03 PMPCANC
Call Anthony to coordinate time. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR18-00010 INSP-Final Inspection1/25/20181/26/20181/26/2018 1:09:27 PMAFAIL
Provide modification to the two strobes to provide coverage as discussed and marked on the plans. Provide proper placement of the duct smoke detectors as discussed and provide testing. The hood suppression system reported as alarm to the FACP but the alarm signals did not report off site. Provide as-builts of changes prior to a final sign off.

Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
FIR18-00034 INSP-Final Inspection1/26/20181/26/20181/26/2018 1:06:26 PMPFAIL
Need plans and documents and the closeout documents. I witnessed the puff test and it functioned correctly and reported to the panel but did not report off site.

Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR17-00773 INSP-Final Inspection1/25/20181/26/20181/26/2018 12:56:39 PMAPASS
Permit finaled


Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00047 INSP-Final Inspection1/25/20181/26/20181/26/2018 11:50:34 AMAFAIL
Not ready for a final. Inspection was for a rough-in. The additional sprinkler coverage in the fire place is ok for cover and the two pendants have been relocated further from the soffits.

call before to meet // Roy Phone #: ###-####
FIR17-00630 INSP-Final Inspection1/24/20181/26/20181/26/2018 11:15:37 AMAFAIL
Contact the plan reviewer for guidance on wether a plan modification is needed or if as-builts will suffice.The one line riser does not match actual points and descriptions such as dry system pressure switch, AES instead of phone lines....ect. Also per dicussion with on site electrician, hvac and general contractor not all of the duct smoke detectors are functional I stated that all devices, as shown on the plans, need to be installed/cunctional/tested or plans will need to be modified to delete the devices. The deleted devices will require a separate permit when installed prior to an occupancy approval for the individual tenants. Today we tested all devices except the flow switch for system #2 and the duct smoke detectors.


This is for Belmont Core Phone #: ###-#### Inspection requested via web by Ken Webster
FIR17-00686 INSP-Final Inspection1/25/20181/26/20181/26/2018 10:32:29 AMAPASS
permit finaled
FIR17-00631 INSP-Final Inspection1/25/20181/26/20181/26/2018 10:31:49 AMAPASS
Permit finaled
FIR17-00593 INSP-Final Inspection1/25/20181/26/20181/26/2018 10:31:07 AMAPASS
Permit finaled
FIR17-00687 INSP-Final Inspection1/25/20181/26/20181/26/2018 10:30:13 AMAFAIL
This permit can be finaled when the flow switch for the sprinkler riser that serves this tenant space has been tested. It currently has no inspectors test for testing of the new flow switch
BLD16-04309 FIRE-Final Inspection1/25/20181/26/20181/26/2018 10:28:34 AMPPASS
life safety passed


Phone #: ###-#### Inspection requested via web by David Scaggs
FIR17-00353 INSP-Final Inspection1/25/20181/26/20181/26/2018 10:27:58 AMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-04588 FIRE-Final Inspection1/25/20181/26/20181/26/2018 10:04:38 AMAPASS
Life safety passed

Spence Phone #: ###-####
BLD16-02806 FIRE-Final Inspection1/25/20181/26/20181/26/2018 8:34:52 AMAFAIL
Provide address, provide permanant exit discharge lighting, mount the occupant load sign, provide testing of the duct smoke detectors.

Phone #: ###-#### Inspection requested via web by Ryan Wilhelm
FIR17-00707 INSP-Final Inspection1/25/20181/26/20181/26/2018 8:33:51 AMAPASS
The hood suppression system shut down the electrical. Permit finaled

Dave Phone #: ###-####
FIR18-00056 INSP-Final Inspection1/25/20181/26/20181/26/2018 8:22:52 AMAPART
Rough-in passed. piping is ok to cover. Not ready for final yet.