FIR19-00034
| INSP-Final Inspection | 1/24/2019 | 1/28/2019 | 1/28/2019 3:03:17 PM | P | CANC |
|
|
Cancel per Nate Phone #: ###-####
|
NAF18-00115
| INSP-Final | 1/28/2019 | 1/28/2019 | 1/28/2019 2:48:15 PM | P | FAIL |
|
|
Provide plan modification that shown the new wall not being built, provide emergency lighting as discussed, provide annual inspection tag for the fire extinguisher, remove the thumbturn deadbolt from the rear exit door.
Call prior to going Phone #: 2089015831 >> Inspection requested via mobile web by Jinny Giery
|
FIR18-00735
| INSP-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 2:45:55 PM | P | FAIL |
|
|
Provide as-builts that show the candella changes and the different fire alarm panel. All devices tested except the duct smoke detectors. The first detector that I looked at is mounted incorrectly. Inspection stopped. All other devices tested and signals verified
|
FIR18-00849
| INSP-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 2:43:18 PM | P | PASS |
|
|
Permit finaled
|
NAF18-00128
| INSP-Sprinkler Rough-in | 1/28/2019 | 1/28/2019 | 1/28/2019 12:49:59 PM | P | PART |
|
|
Rough-in passed. All piping, except as marked on the approved plans, can be covered. Tenting passed. Builder is going to add insulation in the garage area.
Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John
|
FIR18-00623
| INSP-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 12:00:50 PM | P | CANC |
|
|
To be rescheduled per Richard Phone #: ###-####
|
FIR18-00886
| INSP-Sprinkler Rough-in | 1/28/2019 | 1/28/2019 | 1/28/2019 10:55:08 AM | P | CANC |
|
|
Contact Tanner Loomis ###-#### - 30 min prior to RTC Insp Start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR18-00863
| INSP-Final Inspection | 1/27/2019 | 1/28/2019 | 1/28/2019 10:53:30 AM | A | PASS |
|
|
Permit finaled.
please call 1/2 hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
|
BLD18-02281
| FIRE-Final Inspection | 1/24/2019 | 1/28/2019 | 1/28/2019 10:14:18 AM | A | FAIL |
|
|
Inspection was just for the shop area since other work is not complete. To allow use of the shop area the relocated fire hydrant needs tto be approved by plan review, the existing overhead door needs to be removed as per plan for our exit path and the walls the dealer wants to keep shown on a revised building plan, also on the path of egress the thumbturn deadbolt needs to be removed at the exterior exit door and the exit sign over this same door repaired. In the other areas shown to be modified the Storage Room was not built which will need to be addressed on modified approved plans.
Juilan Phone #: ###-####
|
BLD18-03801
| FIRE-Final Inspection | 1/24/2019 | 1/28/2019 | 1/28/2019 9:24:10 AM | A | FAIL |
|
|
Provide ceiling tile, provide testing of the exit signs/emergency lights, repair the exit signs in the elevator lobby, provide fire alarm plan as-builts
Larren Phone #: ###-####
|
FIR18-00872
| INSP-Final Inspection | 1/25/2019 | 1/28/2019 | 1/28/2019 9:09:21 AM | A | PASS |
|
|
Permit finaled
Richard Clark is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00922
| INSP-Sprinkler Rough-in | 1/25/2019 | 1/28/2019 | 1/28/2019 9:08:58 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered
Phone #: ###-#### Inspection requested via web by Sam Ball
|