BLD16-01757
| FIRE-Conference | 1/29/2018 | 1/29/2018 | 1/30/2018 9:10:21 AM | P | DONE |
|
|
I went over life safety requirements with Steve which included the medical gas rooms. Per the electrician the exit discharge lights are controled by a photo cell. Per Chapter 10 of the IFC no allowance is made for this or timers.
Steve Phone #: ###-####
|
FIR07-00757
| FIR-Aging Inspection | 1/29/2018 | 1/29/2018 | 1/30/2018 6:25:49 AM | | NR |
|
|
contractor is out of business
|
FIR05-00021
| FIR-Aging Inspection | 1/29/2018 | 1/29/2018 | 1/30/2018 6:25:15 AM | | NR |
|
|
contractor is out of business
|
FIR17-00772
| INSP-Final Inspection | 1/29/2018 | 1/29/2018 | 1/29/2018 1:46:45 PM | P | PASS |
|
|
Permit finaled.
|
FIR17-00447
| INSP-Sprinkler Rough-in | 1/29/2018 | 1/29/2018 | 1/29/2018 1:29:57 PM | P | PASS |
|
|
Rough-in passed and tenting passed. Piping is ok to cover.
|
BLD16-02806
| FIRE-Final Inspection | 1/28/2018 | 1/29/2018 | 1/29/2018 1:29:23 PM | P | PASS |
|
|
Life safety passed
Final reinspect. Items corrected per notes. Phone #: ###-#### Inspection requested via web by Ryan Wilhelm
|
FIR17-00748
| INSP-Final Inspection | 1/29/2018 | 1/29/2018 | 1/29/2018 12:14:01 PM | P | PASS |
|
|
permit finaled
Call Anthony to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR17-00748
| INSP-Sprinkler Rough-in | 1/29/2018 | 1/29/2018 | 1/29/2018 12:11:27 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR18-00050
| INSP-Sprinkler Rough-in | 1/29/2018 | 1/29/2018 | 1/29/2018 12:01:21 PM | P | PASS |
|
|
Permit finaled
Call Anthony to coordinate, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00058
| INSP-Final Inspection | 1/29/2018 | 1/29/2018 | 1/29/2018 11:14:10 AM | P | PASS |
|
|
Permit finaled
Contact - Leroy Anderson ###-#### 30 min prior to Fire Final Start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00058
| INSP-Sprinkler Rough-in | 1/29/2018 | 1/29/2018 | 1/29/2018 11:13:49 AM | P | PASS |
|
|
Rough-in passed.
|
BLD17-04532
| FIRE-Final Inspection | 1/29/2018 | 1/29/2018 | 1/29/2018 11:13:17 AM | P | CANC |
|
|
To be re-scheduled per Tim
Please call 30 min ahead for access - Tim Phone #: ###-####
|
FIR17-00670
| INSP-Sprinkler Rough-in | 1/29/2018 | 1/29/2018 | 1/29/2018 11:12:33 AM | P | CANC |
|
|
To be re-scheduled per George.
George Jess is the contact for this rough in inspection. He is hoping for an appointment in the pm. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00687
| INSP-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 10:57:39 AM | A | PASS |
|
|
permit finaled
Contact Scott Powada ###-#### 30 min prior to fire final start for Inspectors Test System #1 please.
Thank YOU, Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD17-03830
| FIRE-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 10:00:15 AM | A | FAIL |
|
|
Repair the emergency lights as discussed, provide corrected hardware at the west/front exterior exit door or get plan review approval for the two doors with keyed lock/deadbolts
Jade Phone #: ###-####
|
FIR18-00010
| INSP-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 9:58:47 AM | A | PASS |
|
|
Permit finaled
Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR18-00034
| INSP-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 9:58:23 AM | A | PASS |
|
|
Permit finaled.
Inspection requested via web by Don Kartchner
|
BLD17-02141
| FIRE-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 7:50:40 AM | A | FAIL |
|
|
Need small documents, need four emergency lights repaired, need address, need fire dept signage, need Grading permit inspected/signed off.
Rod Phone #: ###-####
|