Inspections for the day of: Wednesday, January 29, 2020.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00230 INSP-Final Inspection1/29/20201/29/20201/29/2020 3:55:17 PMPCANC
Cancel per discussion with Josiah due to issues with the fire alarm panel.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00365 INSP-Supply line flush1/29/20201/29/20201/29/2020 3:54:38 PMPPASS
Underground supply line flush witnessed.
FIR19-00365 INSP-Sprinkler Rough-in/Hydro1/28/20201/29/20201/29/2020 2:07:05 PMPCANC
Not ready for hydro due to Suez needing an extended flush time because of water discoloration.

Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00816 INSP-Sprinkler Rough-in1/29/20201/29/20201/29/2020 1:59:31 PMPFAIL
need plan mods/as-builts showing the pipe routing changes, need the tenting repaired. No piping can be covered yet.

Ready any time, call James before heading out. Overhead rough and tenting. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD18-04294 FIRE-Final Inspection1/27/20201/29/20201/29/2020 1:56:59 PMPFAIL
See the Fire life safety review comments for items marked in red that need addressed. It includes testing of the three emergency off switches, duct smoke detectors, adding exit discharge lighting at the Store Room exit, removing the dead bolt at the Beer Cooler, removing the thumb turn dead bolts at both main exit doors, providing an operational permit for the tank storage/exchange, 6" island's....ect.

Phone #: ###-#### Inspection requested via web by Roger Graves
FIR19-00599 INSP-Supply line flush1/28/20201/29/20201/29/2020 12:37:40 PMAPASS
Underground supply line flush passed but this is the wrong permit number. Actual permit is FIR19-00365 and an entry has been made there.

Kenny Caldwell will be the contact. Stacey with the water will be there between 10 and 10:30 AM. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00599 INSP-Sprinkler Rough-in1/27/20201/29/20201/29/2020 12:35:14 PMAPASS
Overhead rough-in, branchlines/hangers, for the Kitchen area passed. An additional cover inspection will be needed when T-bar has been installed. Kenny Caldwell is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-04367 FIRE-Final Inspection1/29/20201/29/20201/29/2020 12:27:26 PMPFAIL
Mount the fire extinguisher as discussed and provide the correct Suite number. Plans say 100 tenant wants 300. Please call 15 min. prior to arrival so I can ensure I''m there. Inspection requested via web by Justin Schwartz
BLD19-04769 FIRE-Final Inspection1/29/20201/29/20201/29/2020 12:13:31 PMPPASS
Life safety passed.

Ben Covert Phone #: ###-####
BLD19-04869 FIRE-Final Inspection1/29/20201/29/20201/29/2020 12:12:45 PMPPASS
Life safety passed
FIR20-00044 INSP-Final Inspection1/29/20201/29/20201/29/2020 12:05:10 PMPPASS
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR20-00044 INSP-Sprinkler Rough-in1/29/20201/29/20201/29/2020 12:04:48 PMPPASS
Rough-in passed. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-03877 FIRE-Final Inspection1/28/20201/29/20201/29/2020 9:56:04 AMPPASS
Life safety passed for Bldg #1/Club House.

Final inspection is also scheduled for today. We should be ready anytime. Phone #: ###-#### Inspection requested via web by chad stradley
FIR20-00028 INSP-Sprinkler Rough-in1/27/20201/29/20201/29/2020 9:36:17 AMAPASS
The overhead rough-in passed. Tenting verified. Piping is of for cover. Rough and tenting. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-01275 FIRE-Final Inspection1/27/20201/29/20201/29/2020 8:24:05 AMAPASS
Life safety passed. Contractor to remove the non-functional door mags at the main exit as discussed.

Call prior to arrival, needing to conduct with Fire Final Phone #: ###-#### Inspection requested via web by Roy Moore
FIR19-00679 INSP-Final Inspection1/28/20201/29/20201/29/2020 8:22:11 AMAPASS
Permit finaled.

Plans on site Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00353 INSP-Sprinkler Rough-in1/29/20201/29/20201/29/2020 12:00:00 AMPPART
EQ bracing on 1st floor corridor pass. Piping on 1st floor corridir pass. Fire penetration need to be finished, also patching of sheetrock around EQ bracing needs to be completed and inspected before ok to cover.**MAS**
as late as possible Phone #: ###-#### >> Inspection requested via web by jeremiah robison
FIR20-00050 INSP-Sprinkler Rough-in1/29/20201/29/20201/29/2020 12:00:00 AMPDONE
PASS rough ok to cover**MAS
Phone #: ###-#### >> Inspection requested via web by Sam Ball