Inspections for the day of: Thursday, January 31, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00434 FIRE-Final Inspection1/31/20191/31/20191/31/2019 3:28:30 PMPFAIL
Repair the smoke alarm and provide city approved plans

ZACH Phone #: ###-####
NAF18-00124 INSP-Sprinkler Rough-in1/30/20191/31/20191/31/2019 2:49:01 PMPPART
Inspection was to include the thrid floor but I noted that the concealed space heads are overspaced. Inspection was stopped for the third floor. However sprinkler protection has been added back in the first floor balconies so the interior piping can be covered now on the first floor of the residential (east end) area.


Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
FIR18-00961 INSP-Final Inspection1/30/20191/31/20191/31/2019 2:36:20 PMAPASS
Permit finaled
BLD17-02435 FIRE-Final Inspection1/29/20191/31/20191/31/2019 1:40:31 PMACANC
Cancel per Ann Phone #: ###-####
BLD17-02434 FIRE-Final Inspection1/29/20191/31/20191/31/2019 1:40:12 PMACANC
Cancel per Ann Phone #: ###-####
BLD17-02438 FIRE-Final Inspection1/29/20191/31/20191/31/2019 1:39:55 PMACANC
Cancel per Ann Phone #: ###-#### Cancel per Ann Mofit
FIR18-00642 INSP-Final Inspection1/24/20191/31/20191/31/2019 1:17:22 PMAFAIL
Todays inspection included verifying candellas for the audio/visuals, fire sprinkler risers and smoke detector door release. We were unable to test hvac shutdown due to Target Policy. Plan modifications are required showing the changes strobes, NAC panels, addressing and means of communication. Note IP DACT is installed inproperly and not shown on the plans or battery calcs.


As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
BLD18-02372 FIRE-Final Inspection1/30/20191/31/20191/31/2019 1:14:31 PMAPART
A temporary for life safety until the knox box is provided.

Gary Phone #: ###-####
NAF18-00140 INSP-Supply line flush1/30/20191/31/20191/31/2019 9:43:30 AMAPASS
Underground flush passed
BLD17-02439 FIRE-Final Inspection1/29/20191/31/20191/31/2019 12:00:00 AMACANC
Ann Phone #: ###-#### Cancel per Ann Mofit
BLD17-02436 FIRE-Final Inspection1/29/20191/31/20191/31/2019 12:00:00 AMACANC
Ann Phone #: ###-#### Cancel per Ann Mofit
BLD17-02437 FIRE-Supply Line Hydro1/29/20191/31/20191/31/2019 12:00:00 AMACANC
Ann Phone #: ###-#### Cancel per Ann Mofit