NAF18-00124
| INSP-Conference | 1/4/2019 | 1/7/2019 | 1/7/2019 5:55:45 AM | P | DONE |
|
|
The wrong inspection number was called in Friday but I spoke to Ken about his concerns. Phoenix Fire would like to delete one of the two pendant heads in the rooms where the ceiling fans are now being deleted. I deferred him back to plan review on whether this would be an as-built or a plan modification due to possibly changing the third floor calculation area. Also I stated that any piping changes such as the additional 90's in the piping in the firxt floor southwest area I just inspected would need to be shown.