Inspections for the day of: Tuesday, October 1, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00221 INSP-Sprinkler Rough-in10/1/201910/1/201910/1/2019 2:25:02 PMPPASS
See the city approved plans for the apartment and the third floor corridor where piping is ok for cover.

tOM Phone #: ###-####
FIR19-00561 INSP-Final Inspection9/30/201910/1/201910/1/2019 2:12:17 PMPPASS
Permit finaled. Jeff Phone #: ###-####
FIR19-00372 INSP-Final Inspection9/30/201910/1/201910/1/2019 1:35:48 PMPCANC
Cancel per James. Bell is not working. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00733 INSP-Final Inspection9/30/201910/1/201910/1/2019 1:35:13 PMPCANC
Cancel per Alex. Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00561 INSP-Sprinkler Rough-in10/1/201910/1/201910/1/2019 1:03:20 PMPPASS
Rough-in passed. Piping can be covered.
FIR19-00622 INSP-Sprinkler Rough-in10/1/201910/1/201910/1/2019 12:14:53 PMPPASS
Rough-in passed. Piping can be covered. #: ###-#### Inspection requested via web by Sam Ball
BLD19-03636 FIRE-Final Inspection9/30/201910/1/201910/1/2019 11:34:29 AMAPASS
Life safety passed. Paul Phone #: ###-####
NAF19-00099 INSP-Final9/27/201910/1/201910/1/2019 10:54:59 AMADONE
Permit finaled.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR18-00503 INSP-Final Inspection9/30/201910/1/201910/1/2019 10:09:06 AMAFAIL
For todays inspection I was able to check spaqcing of the south wing and center section first floor. Several devices are overspaced and many more had the candellas set incorrectly. Plans do not match the install such as horns shown but horn/strobes installed (the horn/strobes are required) Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-03627 FIRE-Final Inspection9/30/201910/1/201910/1/2019 8:33:23 AMAFAIL
Provide annual inspection for the fire extinguisher, install door hardware, repair exit sign, remove thumbturn dead bolt, provide entire submittal package. Steve Phone #: ###-####
BLD19-03663 FIRE-Final Inspection9/30/201910/1/201910/1/2019 8:08:07 AMAPASS
Life safety passed. The door to corridor to be provided with single action hardware as discussed prior to a building inspection.. Joan Phone #: ###-####
BLD18-03121 FIRE-Final Inspection9/30/201910/1/201910/1/2019 7:26:53 AMAPART
Life safety complete for apartments 103, 104, 203, 204, 303 and 304. Matt Phone #: ###-####