FIR19-00382
| INSP-Final Inspection | 10/8/2019 | 10/11/2019 | 10/11/2019 4:00:38 PM | P | FAIL |
|
|
Needs breaker lock for final per Lee.
Please call Nate at ###-#### Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00063
| INSP-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 4:00:38 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR18-00892
| INSP-Sprinkler Rough-in | 10/10/2019 | 10/11/2019 | 10/11/2019 3:14:27 PM | P | FAIL |
|
|
No access to the single level and tenting is not correct for the two level area. Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD19-01233
| FIRE-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 3:13:40 PM | A | NR |
|
|
No ready for life safety due to fire alarm resubmittal. Phone #: ###-#### Inspection requested via web by Jimmie Miller
|
BLD19-03591
| FIRE-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 12:43:27 PM | A | PASS |
|
|
Life safety passed.. Per plan review the 8" flu space is ok as compared to the 12" shown on the plan. Phone #: ###-#### Inspection requested via web by Jeff Higgins
|
BLD19-02648
| FIRE-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 11:38:34 AM | A | PASS |
|
|
Life safety passed for a temp as per the scope of work. Amir- for temp occupancy 2nd tel####-#### Phone #: ###-####
|
FIR19-00221
| INSP-Sprinkler Rough-in | 10/10/2019 | 10/11/2019 | 10/11/2019 10:31:22 AM | A | PASS |
|
|
Two dry pendant heads for the trash shoot are ok for cover. Tom Phone #: ###-####
|
NAF19-00028
| INSP-Final | 10/10/2019 | 10/11/2019 | 10/11/2019 10:16:26 AM | A | FAIL |
|
|
Need city approved plans and small documents. Need to verify that the mezzanine that is being used for storage is shown, repair exit signs and provide sticker at main exit and provide fire extinguishers as discussed. Call prior to going Phone #: 2083432621 >> Inspection requested via mobile web by Miranda
|
FIR19-00337
| INSP-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 9:11:18 AM | A | FAIL |
|
|
Tested the induct detectors. Notification needs to acivate for entire building when an alarm condition is present. It currently does not. Need to test the smoke detectors with the hvac units in heat mode to verify correct shut down. Kristen Phone #: ###-####
|