Inspections for the day of: Wednesday, October 16, 2019.
Number of inspections: 31
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03790 FIRE-Conference10/16/201910/16/201910/16/2019 4:25:19 PMPDONE
We went over life safety requirements. I noted sprinkler modifications are needed and it appear additional emergency lights may be needed. No approved plans were on site.
FIR19-00752 INSP-Sprinkler Rough-in10/15/201910/16/201910/16/2019 4:24:09 PMPPASS
The underground supply piping is ok for cover.

UG cover. Will call when ready. Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD18-02802 FIRE-Final Inspection10/16/201910/16/201910/16/2019 4:23:38 PMPPASS
Life safety passed.

Phone #: ###-#### Inspection requested via web by Todd Landvatter
BLD19-02065 FIRE-Final Inspection10/16/201910/16/201910/16/2019 4:22:46 PMPCANC
Need the shell/core building permit finaled first. I spoke to josh about this. jOSH Phone #: ###-####
BLD18-01631 FIRE-Final Inspection10/15/201910/16/201910/16/2019 3:09:29 PMPPASS
Life safety passed. Carrie is to remove the padlock on the east side gate in the fence that the basement and second floor empty into. Carrie Phone #: ###-####
BLD19-04080 FIRE-Final Inspection10/16/201910/16/201910/16/2019 3:02:38 PMPPASS
Life safety passed. Thomas Phone #: ###-####
FIR18-00834 INSP-Final Inspection10/15/201910/16/201910/16/2019 3:02:02 PMPCANC
To be rescheduled due to time constraints due to work load.Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00767 INSP-Final Inspection10/15/201910/16/201910/16/2019 3:01:43 PMPCANC
To be rescheduled due to time constraints due to work load. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR19-00127 INSP-Final Inspection10/16/201910/16/201910/16/2019 3:01:22 PMPCANC
To be rescheduled due to time constraints due to work load. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD18-02497 FIRE-Final Inspection10/15/201910/16/201910/16/2019 3:00:56 PMPCANC
To be rescheduled due to time constraints due to work load. Ken Phone #: ###-####
FIR19-00644 INSP-Final Inspection10/16/201910/16/201910/16/2019 3:00:02 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00646 INSP-Final Inspection10/16/201910/16/201910/16/2019 2:59:39 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00643 INSP-Final Inspection10/16/201910/16/201910/16/2019 2:59:13 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00639 INSP-Final Inspection10/16/201910/16/201910/16/2019 2:58:45 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00641 INSP-Final Inspection10/16/201910/16/201910/16/2019 2:58:21 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00645 INSP-Final Inspection10/16/201910/16/201910/16/2019 2:57:54 PMPFAIL
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
BLD19-00138 FIRE-Final Inspection10/16/201910/16/201910/16/2019 2:29:58 PMPPASS
Life safety passed. Emanuel Phone #: ###-####
NAF19-00048 INSP-Final10/16/201910/16/201910/16/2019 2:12:01 PMPDONE
Permit finaled

Call prior to going Phone #: 2088991516 >> Inspection requested via mobile web by John Looez
FIR18-00778 INSP-Final Inspection10/14/201910/16/201910/16/2019 2:09:25 PMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00867 INSP-Final Inspection10/14/201910/16/201910/16/2019 2:05:34 PMAPASS
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-03790 FIRE-Supply Line Hydro10/15/201910/16/201910/16/2019 12:53:28 PMACANC
Wrong inspection type called in. Should have been conference.
Terry Phone #: ###-####
FIR19-00531 INSP-Sprinkler Rough-in/Hydro10/15/201910/16/201910/16/2019 11:20:59 AMAPASS
The overhead hydro witnessed with no pressure loss. Overhead rough-in passed. I noted that the big a** fans are being installed and may cause obstruction problems. I also noted a piece of equipment being constructed that incorporates some combustible concealed spaces that will need to be addressed as well.

Call 30 mins ahead- Matt Phone #: ###-####
FIR18-00106 INSP-Final Inspection10/15/201910/16/201910/16/2019 10:41:34 AMACANC
Call before please
Thanks,
Jim
###-#### Phone #: ###-#### >> Inspection requested via web by Jim Shilton Inspection cancelled from web by: Jim Shilton
FIR19-00337 INSP-Final Inspection10/16/201910/16/201910/16/2019 10:19:30 AMPPASS
Permit finaled
NAF18-00086 INSP-Final10/15/201910/16/201910/16/2019 10:16:00 AMADONE
Permit finaled

Contact Noemi Carrero ###-#### 30 min prior to Final Insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-00751 FIRE-Final Inspection10/15/201910/16/201910/16/2019 9:29:27 AMAPASS
Life safety passed. No card on site to sign.

7am
Phone #: ###-#### Inspection requested via web by James Hibbard
FIR18-00957 INSP-Conference10/15/201910/16/201910/16/2019 9:19:47 AMADONE
Nacho, Rick and I discussed the fire place just inside the main entry. Per Nacho he will wrap the fire place with fire treated wood to be verified by myself and the building inspector. I also noted a raised platform has been built in the south east corner of the building that wil need to be addressed as far as a combustible concealed space. Rick Phone #: ###-####
BLD19-00751 FIRE-Alarm Testing10/15/201910/16/201910/16/2019 7:30:58 AMAFAIL
Fire alarm testing needs to be scheduled with the project related FIR permit. 7am
Phone #: ###-#### Inspection requested via web by James Hibbard
BLD19-01312 FIRE-Conference10/15/201910/16/201910/16/2019 12:00:00 AMADONE
** Met with Tom. Discussed exit lighting, fire sprinkler, and fire alarm placement questions he had. He is going to meet with the architect to go over items we discussed.**MAS***Tom Phone #: ###-####
FIR19-00418 INSP-Final Inspection10/16/201910/16/201910/16/2019 12:00:00 AMAFAIL
***Failed - None of the items on the last inspection have been corrected. MAS***
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
BLD19-01233 FIRE-Final Inspection10/11/201910/16/201910/11/2019 5:20:36 PMACANC
Please come first thing (7 am) so we can get done before school starts. We cant sound alarm when school in session. Thank you. Phone #: ###-#### >> Inspection requested via web by Jackie Phelps Inspection cancelled from web by: Jackie Phelps