FIR19-00365
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/17/2019 | 10/17/2019 4:39:50 PM | P | CANC |
|
|
Cancel per Kenny Caldwell. Also wrong permit called in. We appreciate your help. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00221
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/17/2019 | 10/17/2019 3:39:55 PM | P | CANC |
|
|
WIll need to be rescheduled. Can not make it due to work load and personell shortage. 1st floor- Tom Phone #: ###-####
|
FIR18-00834
| INSP-Final Inspection | 10/17/2019 | 10/17/2019 | 10/17/2019 3:34:52 PM | P | PASS |
|
|
Permit finaled
Todd Ketterling is the contact. This inspection should have already taken place, this is just the paper trail. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00662
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/17/2019 | 10/17/2019 3:30:08 PM | P | CANC |
|
|
Will need to be rescheduled. Can not make it due to work load and personell shortage. Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-02882
| FIRE-Final Inspection | 10/17/2019 | 10/17/2019 | 10/17/2019 3:27:53 PM | P | CANC |
|
|
To be rescheduled for tomorrow morning. MIKE Phone #: ###-####
|
FIR19-00445
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 2:32:58 PM | A | PASS |
|
|
Permit finaled.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00585
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 2:12:03 PM | A | PASS |
|
|
Permit finaled.
Call ahead to Brian if you need him to meet onsite to verify candela changed. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD17-02262
| FIRE-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 2:05:43 PM | A | PASS |
|
|
Previous corrections have been addressed. Life safety passed. Tony Phone #: ###-####
|
BLD17-02261
| FIRE-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 2:05:10 PM | A | FAIL |
|
|
Replace the ceiling that has been removed for the installation of the security grill. All other corrections have been addressed.
Tony Phone #: ###-####
|
FIR19-00684
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 1:24:38 PM | A | FAIL |
|
|
Tested all devices but the new smoke detector in the main corridor is not centered on the doors as required in nfpa 72.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00452
| INSP-Final Inspection | 10/15/2019 | 10/17/2019 | 10/17/2019 12:42:57 PM | A | PASS |
|
|
Permit finaled. Previous corrections addressed.
Phone #: ###-#### Inspection requested via web by Jason Heath
|
BLD18-02497
| FIRE-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 12:14:56 PM | A | FAIL |
|
|
No inspection performed. No city approved plans or small documents on site. Ken Phone #: ###-####
|
FIR19-00767
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 12:03:46 PM | A | PASS |
|
|
Permit finaled.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00127
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 12:02:41 PM | A | PASS |
|
|
Permit finaled.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00106
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 11:57:42 AM | A | FAIL |
|
|
I witnessed the testing of the two heat detectors on the elevator penthouse, as marked on the plans, and they shunt the two elevators. I witnessed the penthouse smoke detector recall the eelvator to the 1st floor. We then went to the 9th floor and tripped the elevator lobby detector and the elevator did nothing and actually continued to function as normal.. Testing was stopped.
Please call me prior to arrival so we can prepare. State Elevator Inspector will make provisions to allow city to inspect permitted 2 new elevators.
Phone #: ###-#### Inspection requested via web by Jim Shilton
|
FIR19-00068
| INSP-Sprinkler Rough-in | 10/16/2019 | 10/17/2019 | 10/17/2019 11:51:49 AM | A | PASS |
|
|
The pendant heads in the Lobby passed rough-in. Piping can be covered.
Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
FIR19-00718
| INSP-Sprinkler Rough-in/Hydro | 10/16/2019 | 10/17/2019 | 10/17/2019 8:44:14 AM | P | FAIL |
|
|
Overhead hydro failed due to sheetrock workers opening valve
Call James before heading out, hydro only while it is warm enough. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00570
| INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | A | FAIL |
|
|
***FAIL Head plugged in RM106 MEP. No stamped plans on site. Unable to get ahold of contact MAS***
Mike Phone #: ###-####
|
FIR19-00654
| INSP-Sprinkler Rough-in/Hydro | 10/16/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | A | PASS |
|
|
*** PASS Hydro Only - No rough inspection done at this time. MAS***
George Jess is the contact for this overhead hydro. We appreciate your help. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR19-00722
| INSP-Sprinkler Rough-in | 10/16/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | P | PART |
|
|
** Pass Partial Rough OK to cover hard lids in offices. MAS***
Jimmy is your contact Phone #: ###-#### >> Inspection requested via web by Chris Green
|
BLD19-02603
| FIRE-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | P | FAIL |
|
|
*** FAIL No ceiling tiles installed. Fire sprinklers not installed in tiles. Duct wrap needs repaired in 2 places where sitting on grid. MAS***
Dave Phone #: ###-####
|
FIR19-00729
| INSP-Final Inspection | 10/17/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | P | FAIL |
|
|
*** FAIL No ceiling tiles installed. Heads not installed in tiles. MAS***
We would like to perform this inspection in conjunction with fire lie safety final for bld.
Please call Logan with questions and time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham
|
FIR19-00674
| INSP-Sprinkler Rough-in | 10/16/2019 | 10/17/2019 | 10/17/2019 12:00:00 AM | P | PART |
|
|
*** PASS Partial underground. Area inspected is marked on stamped plans. OK to cover inspected area only. MAS***
This inspection is for cover for underground piping. Troy Nelson will call when ready. Phone #: ###-#### >> Inspection requested via web by Daniel Buccino
|