Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00365 INSP-Sprinkler Rough-in10/17/201910/17/201910/17/2019 4:39:50 PMPCANC
Cancel per Kenny Caldwell. Also wrong permit called in. We appreciate your help. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00221 INSP-Sprinkler Rough-in10/17/201910/17/201910/17/2019 3:39:55 PMPCANC
WIll need to be rescheduled. Can not make it due to work load and personell shortage. 1st floor- Tom Phone #: ###-####
FIR18-00834 INSP-Final Inspection10/17/201910/17/201910/17/2019 3:34:52 PMPPASS
Permit finaled

Todd Ketterling is the contact. This inspection should have already taken place, this is just the paper trail. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00662 INSP-Sprinkler Rough-in10/17/201910/17/201910/17/2019 3:30:08 PMPCANC
Will need to be rescheduled. Can not make it due to work load and personell shortage. Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-02882 FIRE-Final Inspection10/17/201910/17/201910/17/2019 3:27:53 PMPCANC
To be rescheduled for tomorrow morning. MIKE Phone #: ###-####
FIR19-00445 INSP-Final Inspection10/16/201910/17/201910/17/2019 2:32:58 PMAPASS
Permit finaled.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00585 INSP-Final Inspection10/16/201910/17/201910/17/2019 2:12:03 PMAPASS
Permit finaled.

Call ahead to Brian if you need him to meet onsite to verify candela changed. Phone #: ###-#### Inspection requested via web by Kristin Dolan
BLD17-02262 FIRE-Final Inspection10/16/201910/17/201910/17/2019 2:05:43 PMAPASS
Previous corrections have been addressed. Life safety passed. Tony Phone #: ###-####
BLD17-02261 FIRE-Final Inspection10/16/201910/17/201910/17/2019 2:05:10 PMAFAIL
Replace the ceiling that has been removed for the installation of the security grill. All other corrections have been addressed.

Tony Phone #: ###-####
FIR19-00684 INSP-Final Inspection10/16/201910/17/201910/17/2019 1:24:38 PMAFAIL
Tested all devices but the new smoke detector in the main corridor is not centered on the doors as required in nfpa 72.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
FIR19-00452 INSP-Final Inspection10/15/201910/17/201910/17/2019 12:42:57 PMAPASS
Permit finaled. Previous corrections addressed.

Phone #: ###-#### Inspection requested via web by Jason Heath
BLD18-02497 FIRE-Final Inspection10/16/201910/17/201910/17/2019 12:14:56 PMAFAIL
No inspection performed. No city approved plans or small documents on site. Ken Phone #: ###-####
FIR19-00767 INSP-Final Inspection10/16/201910/17/201910/17/2019 12:03:46 PMAPASS
Permit finaled.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR19-00127 INSP-Final Inspection10/16/201910/17/201910/17/2019 12:02:41 PMAPASS
Permit finaled.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00106 INSP-Final Inspection10/16/201910/17/201910/17/2019 11:57:42 AMAFAIL
I witnessed the testing of the two heat detectors on the elevator penthouse, as marked on the plans, and they shunt the two elevators. I witnessed the penthouse smoke detector recall the eelvator to the 1st floor. We then went to the 9th floor and tripped the elevator lobby detector and the elevator did nothing and actually continued to function as normal.. Testing was stopped.

Please call me prior to arrival so we can prepare. State Elevator Inspector will make provisions to allow city to inspect permitted 2 new elevators.

Phone #: ###-#### Inspection requested via web by Jim Shilton
FIR19-00068 INSP-Sprinkler Rough-in10/16/201910/17/201910/17/2019 11:51:49 AMAPASS
The pendant heads in the Lobby passed rough-in. Piping can be covered.

Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
FIR19-00718 INSP-Sprinkler Rough-in/Hydro10/16/201910/17/201910/17/2019 8:44:14 AMPFAIL
Overhead hydro failed due to sheetrock workers opening valve

Call James before heading out, hydro only while it is warm enough. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00570 INSP-Final Inspection10/16/201910/17/201910/17/2019 12:00:00 AMAFAIL
***FAIL Head plugged in RM106 MEP. No stamped plans on site. Unable to get ahold of contact MAS***
Mike Phone #: ###-####
FIR19-00654 INSP-Sprinkler Rough-in/Hydro10/16/201910/17/201910/17/2019 12:00:00 AMAPASS
*** PASS Hydro Only - No rough inspection done at this time. MAS***
George Jess is the contact for this overhead hydro. We appreciate your help. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR19-00722 INSP-Sprinkler Rough-in10/16/201910/17/201910/17/2019 12:00:00 AMPPART
** Pass Partial Rough OK to cover hard lids in offices. MAS***
Jimmy is your contact Phone #: ###-#### >> Inspection requested via web by Chris Green
BLD19-02603 FIRE-Final Inspection10/16/201910/17/201910/17/2019 12:00:00 AMPFAIL
*** FAIL No ceiling tiles installed. Fire sprinklers not installed in tiles. Duct wrap needs repaired in 2 places where sitting on grid. MAS***
Dave Phone #: ###-####
FIR19-00729 INSP-Final Inspection10/17/201910/17/201910/17/2019 12:00:00 AMPFAIL
*** FAIL No ceiling tiles installed. Heads not installed in tiles. MAS***
We would like to perform this inspection in conjunction with fire lie safety final for bld.

Please call Logan with questions and time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham
FIR19-00674 INSP-Sprinkler Rough-in10/16/201910/17/201910/17/2019 12:00:00 AMPPART
*** PASS Partial underground. Area inspected is marked on stamped plans. OK to cover inspected area only. MAS***
This inspection is for cover for underground piping. Troy Nelson will call when ready. Phone #: ###-#### >> Inspection requested via web by Daniel Buccino