FIR18-00106
| INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/21/2019 9:56:46 AM | A | PART |
|
|
A life safety temp for the use of the two elevators is being given with boise fire permission with the states acceptance. The acceptance paperwork is attached to this permit. Per dicussion with Jim Shilton these elvators will still need to be re-inspected by the fire code inspector prior to a final sign off as discussed.
Phone #: ###-#### Inspection requested via web by Jim Shilton
|
FIR19-00207
| INSP-Final Inspection | 10/18/2019 | 10/18/2019 | 10/18/2019 3:40:53 PM | P | PASS |
|
|
Permit finaled. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00634
| INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 3:26:33 PM | P | CANC |
|
|
I'm unable to perform the inspection when the contractor was ready. The site requested that the inspection start at 2:00 pm if possible since they have several meetings during the day. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR17-00400
| INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 3:25:40 PM | P | PASS |
|
|
Permit finaled
Jake Adams (BSD) will be on site with copy of plans. We finally have a clean FACP! Please call Jake 30 minutes prior to Inspector arrival. Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
BLD19-03790
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 3:23:45 PM | P | CANC |
|
|
Need the project related fire sprinkler permit finaled prior to a fire life safety inspection. Terry Phone #: ###-####
|
BLD18-03122
| FIRE-Final Inspection | 10/18/2019 | 10/18/2019 | 10/18/2019 2:31:22 PM | P | PART |
|
|
Life safety on units 101 202 203 302 303 103 104 203 204 303 304 is complete. 102 had a smoke alarm too close to the restroom door. // Matt ###-####
|
FIR19-00595
| INSP-Sprinkler Rough-in | 10/18/2019 | 10/18/2019 | 10/18/2019 2:26:32 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered. Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-02934
| FIRE-Conference | 10/18/2019 | 10/18/2019 | 10/18/2019 1:29:34 PM | P | DONE |
|
|
The project superintendant and I discussed door hardware issues on doors #2 and #3. #2 shows to be deleted and #3 says to have panic. Right now they are both keyed deadbolts.
|
FIR19-00111
| INSP-Final Inspection | 10/14/2019 | 10/18/2019 | 10/18/2019 1:15:47 PM | A | CANC |
|
|
Cancel per Noemi due to the project related fire alarm not being ready. Contact Noemi Carrero ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00404
| INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 12:30:55 PM | A | CANC |
|
|
Cancel per Jon Beazer since he can not be there when I can be there. . We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00317
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 12:13:18 PM | A | FAIL |
|
|
Need fire review notes and all small documents, the site and building address/number need to match the permit documents, provide lever hardware as per the approved door schedule, provide clearance at the fire hydrants..Inspection stopped.
Larry Phone #: ###-####
|
BLD19-03132
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 11:48:54 AM | A | PASS |
|
|
Life safety passed. Ok for life safety permanant. Jonathan Phone #: ###-####
|
FIR19-00374
| INSP-Final Inspection | 10/18/2019 | 10/18/2019 | 10/18/2019 11:32:53 AM | A | PART |
|
|
Fire sprinkler work complete in 105, 106, 205, 206, 305 and 306
|
BLD18-04112
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 10:37:46 AM | A | PART |
|
|
A temporary for life safety is ok with the fire dept approval until the existing fire dept access as been modified as discussed to cut back the trees and provide a ramp. jay Phone #: ###-####
|
BLD18-02497
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 10:10:09 AM | A | FAIL |
|
|
Provide information for the change to a diesel gererator, provide testing of the automatic switch over of the generator since it did not function, provide signage for the gererator as discussed, provide testing of the exit signs and emergency lights, provide fire lane signage. See the review comments for items marked in blue.
Ken Phone #: ###-####
|
FIR19-00668
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/18/2019 | 10/18/2019 10:01:51 AM | A | PASS |
|
|
Rrough-in passed. Piping can be covered.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
NAF19-00003
| INSP-Final | 10/17/2019 | 10/18/2019 | 10/18/2019 9:46:38 AM | A | DONE |
|
|
Life safety passed.
Call prior to going Phone #: 2086972714 >> Inspection requested via mobile web by BRAD COOPER
|
NAF19-00104
| INSP-Final | 10/17/2019 | 10/18/2019 | 10/18/2019 9:46:09 AM | A | DONE |
|
|
Permit finaled
RICK FRY Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR17-00626
| INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 9:14:39 AM | A | PART |
|
|
Fire alarm work complete for phase 4. See the city approved plans for the clouded area in red for the specific devices witnessed.
Brian Phone #: ###-####
|
BLD19-02882
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 8:46:16 AM | A | PASS |
|
|
Life safety passed.
Phone #: ###-####
|
FIR19-00662
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/18/2019 | 10/18/2019 8:44:58 AM | A | PASS |
|
|
The remaining underground supply piping is ok for cover. Bryan Collins is requesting a Underground Rough in Inspection.
Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-02065
| FIRE-Final Inspection | 10/17/2019 | 10/18/2019 | 10/18/2019 12:00:00 AM | A | PASS |
|
|
**PASS Fire Final. Tenant GC still waiting on core&shell to be finaled. Perm Occ signed.MAS**
josh Phone #: ###-####
|
FIR18-00892
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/18/2019 | 10/17/2019 2:20:30 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|