BLD17-00066
| FIRE-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 4:52:58 PM | P | CANC |
|
|
Canceled due to work load. Kelly Phone #: ###-####
|
BLD18-03423
| FIRE-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 4:35:49 PM | P | PART |
|
|
A temporary for life safety has been approved per Joe Bruce. Still need the project related fire alarm permit issued/finaled prior to a final life safety inspection.
Eric Phone #: ###-####
|
FIR19-00404
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 4:31:46 PM | P | FAIL |
|
|
Water has not been piped to the riser.
Jon Beazer is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00531
| INSP-Sprinkler Rough-in/Hydro | 10/21/2019 | 10/21/2019 | 10/21/2019 4:30:13 PM | P | CANC |
|
|
Canceled due to time constraints. Matt- approved plans are in the riser room in yellow manilla folder Phone #: ###-####
|
BLD19-04040
| FIRE-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 4:26:38 PM | P | CANC |
|
|
Canceled due to time constraints.
Call to meet // Shane Phone #: ###-####
|
FIR19-00666
| INSP-Sprinkler Rough-in | 10/21/2019 | 10/21/2019 | 10/21/2019 4:15:23 PM | P | CANC |
|
|
Canceled due to time constraints;. Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|
FIR18-00892
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/21/2019 | 10/21/2019 3:31:50 PM | A | FAIL |
|
|
Not enough access provided to verify tenting. Provide additional access and a letter as discussed for owner to take responcibility for work performed on the tenting as discussed. Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR19-00570
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 3:29:57 PM | A | CANC |
|
|
Canceled due to time constraints. Mike Phone #: ###-####
|
FIR19-00610
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:52:34 PM | P | CANC |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, October 21, 2019.
|
FIR19-00418
| INSP-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 2:39:56 PM | A | CANC |
|
|
Canceled due to time constraints. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-03790
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:34:53 PM | A | PASS |
|
|
Life safety passed.
Terri Phone #: ###-####
|
FIR19-00777
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:33:41 PM | A | PASS |
|
|
Permit finaled.
Kenny Caldwell Field Contact. Thanks for all your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00777
| INSP-Sprinkler Rough-in | 10/18/2019 | 10/21/2019 | 10/21/2019 2:33:19 PM | A | PASS |
|
|
Rough-in passed.
Kenny Caldwell field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-01635
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:32:42 PM | A | CANC |
|
|
To be rescheduled per Steve Phone #: ###-####
|
FIR17-00178
| INSP-Alarm Testing | 10/21/2019 | 10/21/2019 | 10/21/2019 2:32:15 PM | P | CANC |
|
|
To be rescheduled per paul ###-####
|
FIR19-00401
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:17:57 PM | A | PASS |
|
|
Permit finaled
Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR19-00431
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:17:30 PM | A | PASS |
|
|
Permit finaled
Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR19-00494
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:17:01 PM | A | PASS |
|
|
Permit finaled
Dave Phone #: ###-####
|
FIR19-00698
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:16:09 PM | A | CANC |
|
|
This permit will be voided per contact due to work being covered under another pernit.
Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
BLD18-04118
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 2:07:20 PM | A | PASS |
|
|
Life safety passed.
DAN- CALL 30 PRIOR MEET@ BUILD 26 LOBBY Phone #: ###-####
|
FIR19-00599
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/21/2019 | 10/21/2019 1:59:21 PM | A | CANC |
|
|
Cancel per Kenny Caldwell. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00758
| INSP-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 12:03:05 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner
|
FIR19-00679
| INSP-Sprinkler Rough-in | 10/18/2019 | 10/21/2019 | 10/21/2019 11:52:46 AM | A | PASS |
|
|
The two hard lids piping is ok for cover. . Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-02603
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 11:15:29 AM | A | PASS |
|
|
Life safety passed. The building inspector is going to verify the door hardware on the office.
Dave Phone #: ###-####
|
FIR19-00729
| INSP-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 11:14:23 AM | P | PASS |
|
|
Permit finaled.
Please call Logan with Questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD19-02656
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 10:23:12 AM | A | PASS |
|
|
Life safety passed. Per Boise City addressing dept the project address is not an issue.
Matt Phone #: ###-####
|
FIR19-00704
| INSP-Final Inspection | 10/21/2019 | 10/21/2019 | 10/21/2019 10:18:13 AM | P | CANC |
|
|
Call before heading out, ready any time. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD18-02497
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 9:59:08 AM | A | CANC |
|
|
To be canceled per Ken since they are still having generator issues. Ken Phone #: ###-####
|
BLD18-03122
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 9:51:15 AM | A | FAIL |
|
|
The smoke alarm in 102 still has not been relocated.
Matt Phone #: ###-####
|
FIR19-00544
| INSP-Sprinkler Rough-in | 10/21/2019 | 10/21/2019 | 10/21/2019 9:35:33 AM | P | CANC |
|
|
Contact Noemi Carrero - ###-#### 30 mi prior to RTC Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR19-00544
| INSP-Sprinkler Rough-in | 10/21/2019 | 10/21/2019 | 10/21/2019 9:23:16 AM | P | CANC |
|
|
Contact Noemi Carrero ###-#### 30 Min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR19-00221
| INSP-Sprinkler Rough-in | 10/17/2019 | 10/21/2019 | 10/21/2019 8:56:21 AM | A | FAIL |
|
|
I left two messages for contact. Was at site but could not even park due to hyster. Do not have time to look site over for the contact. 1st floor - Tom Phone #: ###-####
|
FIR19-00777
| INSP-Sprinkler Rough-in | 10/21/2019 | 10/21/2019 | 10/21/2019 8:44:04 AM | A | FAIL |
|
|
The two flex heads need to be approved to be installed.
|
FIR19-00374
| INSP-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 8:39:50 AM | A | PASS |
|
|
Permit finaled
Gabe Garduno is the field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-01233
| FIRE-Final Inspection | 10/18/2019 | 10/21/2019 | 10/21/2019 7:31:41 AM | A | PASS |
|
|
Life safety passed. Thank you. Phone #: ###-#### Inspection requested via web by Jackie Phelps
|