Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00748 INSP-Sprinkler Rough-in/Hydro10/23/201910/23/201910/23/2019 3:19:34 PMPPASS
Underground hydro test witnessed with no pressure loss.

Please call Troy Nelson. Underground Hydro Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD19-03835 FIRE-Final Inspection10/22/201910/23/201910/23/2019 1:14:35 PMAPASS
Life safety passed.

Please call 20 min before Phone #: ###-#### Inspection requested via web by Jeff Higgins
FIR19-00556 INSP-Final Inspection10/22/201910/23/201910/23/2019 12:06:28 PMAPASS
Permit finaled.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04054 FIRE-Final Inspection10/22/201910/23/201910/23/2019 11:33:12 AMAPASS
Life safety passed.

aSHLEY Phone #: ###-####
FIR19-00708 INSP-Final Inspection10/22/201910/23/201910/23/2019 11:14:09 AMAFAIL
Tested only the interconnect with the wet system tamper switches and flow switches, other devices have not been connected yet. The monitoring company received the wrong count of signals.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
FIR19-00654 INSP-Sprinkler Rough-in10/22/201910/23/201910/23/2019 11:12:18 AMAFAIL
Resubmit plan mods showing the use of the flex heads. Also provide verification of the upright coverage around the rooms with no ceilings.. No piping can be covered.

George Jess Field Contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00654 INSP-Final Inspection10/22/201910/23/201910/23/2019 11:09:53 AMACANC
Not ready for a final.

George Jess is field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus