BLD18-04112
| FIRE-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 2:50:44 PM | P | FAIL |
|
|
The fire dept access needs addressed as discussed, need K class fire extinguisher, need thumbturn deadbolt on Kitchen door addressed, need the project related fire alarm and hood suppression permits finaled. Jay Phone #: ###-####
|
FIR19-00732
| INSP-Final Inspection | 10/3/2019 | 10/3/2019 | 10/3/2019 2:28:47 PM | P | CANC |
|
|
The project related fire alarm sysem/permit was not ready.
Attempting to test the alarm system as well. Wondering if 330 would work so all the children are out of the school. Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR19-00445
| INSP-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 2:22:55 PM | P | FAIL |
|
|
Ceiling mounted strobes are overspaced in the Kitchen. Inspection stopped. Devices need to be relocated or candellas adjusted. The fire alam plans need to be reviewed by the engineer of record prior to plan review approval. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-02966
| FIRE-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 1:36:22 PM | A | FAIL |
|
|
Provide exit discharge lights at both exits per approved plans and provide emergency lighting just inside of the main exit as per plans. Neil Phone #: ###-####
|
BLD19-03138
| FIRE-Final Inspection | 10/3/2019 | 10/3/2019 | 10/3/2019 1:28:40 PM | P | PASS |
|
|
Life safety passed. Sid Phone #: ###-####
|
FIR19-00740
| INSP-Final Inspection | 10/2/2019 | 10/3/2019 | 10/3/2019 1:28:19 PM | A | PASS |
|
|
Permit finaled
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
BLD19-03087
| FIRE-Final Inspection | 10/3/2019 | 10/3/2019 | 10/3/2019 11:24:34 AM | P | PASS |
|
|
Life safety passed. Per plan review the single door out of the exterior of the warehouse, as shown on the plans, is not required. josh Phone #: ###-####
|
FIR19-00598
| INSP-Sprinkler Rough-in | 10/2/2019 | 10/3/2019 | 10/3/2019 10:48:57 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered. Adam Phone #: ###-####
|
FIR19-00599
| INSP-Sprinkler Rough-in | 10/2/2019 | 10/3/2019 | 10/3/2019 10:39:20 AM | P | PASS |
|
|
Corrections have been made at the two restrooms. Also see the city approved plans for an additional area where the rough-in has passed dated today. Kenny Caldwell is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
NAF19-00052
| INSP-Final | 10/2/2019 | 10/3/2019 | 10/3/2019 9:39:43 AM | A | DONE |
|
|
Life safety passed. No equipment or storage racks have been installed. Fans have not been installed and are state for future. Call prior to going Phone #: 2086972714 >> Inspection requested via mobile web by BRAD Looper
|
NAF19-00081
| INSP-Final | 10/1/2019 | 10/3/2019 | 10/3/2019 9:37:45 AM | A | DONE |
|
|
Permit finaled. RUDY CATIC Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
NAF19-00081
| INSP-Sprinkler Rough-in | 10/3/2019 | 10/3/2019 | 10/3/2019 9:37:11 AM | P | PASS |
|
|
Rough-in passed. Remaining piping can be covered. Call Jeff if there are questions. Thanks Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00716
| INSP-Sprinkler Rough-in | 10/2/2019 | 10/3/2019 | 10/3/2019 8:42:30 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered. Payton Phone #: ###-####
|
FIR19-00382
| INSP-Final Inspection | 9/27/2019 | 10/3/2019 | 10/2/2019 3:53:41 PM | A | CANC |
|
|
Please call Nate at ###-#### Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|