Inspections for the day of: Friday, October 4, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02473 FIRE-Final Inspection10/3/201910/4/201910/4/2019 3:11:29 PMPFAIL
Remove the thumbturn deadbolt at the main exit (keyed ok), provide annual inspection for the fire extinguishers, mount the fire extinguishers no higher than 5', remove the chain/padlock from door as per discussion.


Sherry Phone #: ###-####
BLD17-03056 FIRE-Final Inspection10/3/201910/4/201910/4/2019 3:11:06 PMPFAIL
Remove the thumbturn deadbolt at the main exit (keyed ok), provide annual inspection for the fire extinguishers, mount the fire extinguishers no higher than 5', remove the chain/padlock from door as per discussion.

Sherry Phone #: ###-####
FIR18-00503 INSP-Alarm Testing10/4/201910/4/201910/4/2019 12:43:27 PMPFAIL
The smoke detectors are not reporting to the facp. Inspection stopped. The receiver troubles have been cleared.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00718 INSP-Sprinkler Rough-in10/3/201910/4/201910/4/2019 10:51:41 AMAFAIL
Tenting inspection failed due to modifications needed to block out cold air from entering the area under the second floor. I met with the builder and discussed it. As Built plan is already in progress and will be submitted to Mark within the next few days. Call James if there are any issues, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-02563 FIRE-Final Inspection10/3/201910/4/201910/4/2019 10:37:43 AMAFAIL
Provide permit to relocate the smoke detector and delete the monitor module for the suppression system that is being deleted, provide permit to demo the hood suppression system, provide fire extinguisher as discussed, test the smoke evac system,

Joe Phone #: ###-####
FIR19-00591 INSP-Final Inspection10/3/201910/4/201910/4/2019 9:53:49 AMAPASS
Permit finaled. Javier Blanco Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00741 INSP-Final Inspection10/3/201910/4/201910/4/2019 9:01:35 AMACANC
Not ready for final due to insulation blocking upright sprinkler heads. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00741 INSP-Sprinkler Rough-in10/3/201910/4/201910/4/2019 9:01:05 AMAPASS
Rough-in passed. Can not final until the insulation that is falling from the deck has been repaired. Phone #: ###-#### Inspection requested via web by Sam Ball
NAF19-00104 INSP-Sprinkler Rough-in10/3/201910/4/201910/4/2019 8:44:43 AMAPASS
See the city approved plans for the two hardlids where the sprinkler piping is ok for cover. Please call Rudy with time frame. Thanks Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR19-00337 INSP-Final Inspection10/3/201910/4/201910/4/2019 8:22:13 AMAFAIL
See the city approved plans for notification corrections that are needed. I also noted that the door magnets that have been installed at the main exit may need to be connected to the fire alarm system as per IFC chapter 10.
This hospital is occupied and the test needs to be @ 7 am. Phone #: ###-#### Inspection requested via web by Kristin Dolan
BLD19-00751 FIRE-Final Inspection10/3/201910/4/201910/4/2019 8:21:00 AMAFAIL
Need the project related fire alarm and fire sprinkler permits finaled. I noted that doors have been revised but there were no stamped plans showing the changes had been approved on site. The single main exit door has been changed to a double door with door magnets. It appears to need to meet IFC chapter 10 "sensor controled door" which will require a sensor and interconnection with the fire alarm system. Please contact Jim at ###-####
FIR19-00325 INSP-Final Inspection10/3/201910/4/201910/4/2019 8:19:20 AMAFAIL
Need as-builts prior to a final
FIR19-00591 INSP-Final Inspection10/3/201910/4/201910/3/2019 2:00:35 PMACANC
Mike Oswald Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist Inspection cancelled from web by: Brodie Stenquist