Inspections for the day of: Wednesday, October 9, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00718 INSP-Sprinkler Rough-in10/8/201910/9/201910/9/2019 3:05:20 PMAPASS
Tenting inspection passed. Piping can be covered. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00503 INSP-Alarm Testing10/9/201910/9/201910/9/2019 2:00:32 PMPDONE
Todays inspection we tested the smoke detectors in the first floor central area and the north wing. All tested ok. We set off the notification for the entire building and I noted that the visual devices have two patterns which is ok but the audible devices do not sync which is not ok as per NFPA 72.
Also the smoke detectors are reporting correctly.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00733 INSP-Final Inspection10/9/201910/9/201910/9/2019 2:00:31 PMPFAIL
The micro switches are wired incorrectly and the system is not connected to the facp. No testing performed.

Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00531 INSP-Supply line flush10/8/201910/9/201910/9/2019 11:23:19 AMPCANC
This is going to be a supply line flush inspection. Please contact Heath Day prior to heading to job site at Phone #: ###-#### >> Inspection requested via web by Matt Barnard Inspection cancelled from web by: Matt Barnard
BLD19-01808 FIRE-Final Inspection10/9/201910/9/201910/9/2019 11:16:01 AMAPASS
Life safety passed.

Inspection of new classroom doors so we can change temp occupancy to full occupancy. Please call me when you''re headed that way so I can meet you. Thanks. Phone #: ###-#### Inspection requested via web by Mike Walling
FIR17-00626 INSP-Final Inspection10/8/201910/9/201910/9/2019 10:35:17 AMAFAIL
On site fire man asked us to reschedule since they are using the phase 4 area. Brian Phone #: ###-####
BLD19-00138 FIRE-Final Inspection10/8/201910/9/201910/9/2019 10:25:09 AMACANC
Wasx supposed to be scheduled for monday per contact

Emanuel Phone #: ###-####