FIR18-00546
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/15/2018 2:41:33 PM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD17-03648
| FIRE-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 4:50:24 PM | P | FAIL |
|
|
Life safety will be ok to final when the project related fire alarm and fire sprinkler permit is addressed.
Tony Phone #: ###-####
|
FIR18-00414
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 4:49:05 PM | A | FAIL |
|
|
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00333
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 4:48:37 PM | P | FAIL |
|
|
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD15-02318
| FIRE-Final Inspection | 10/26/2018 | 11/14/2018 | 11/14/2018 3:05:55 PM | P | PASS |
|
|
life safety passed
Please call ahead for access - Cody Phone #: ###-####
|
BLD15-02316
| FIRE-Final Inspection | 10/26/2018 | 11/14/2018 | 11/14/2018 3:05:15 PM | P | PASS |
|
|
life safety passed
Please call ahead for access - Cody Phone #: ###-####
|
FIR18-00298
| INSP-Sprinkler Rough-in | 11/13/2018 | 11/14/2018 | 11/14/2018 2:51:25 PM | P | PASS |
|
|
The additional hangers have been added. Will verify the 4 way brace at the riser during the final. All piping can be covered. Still need submittals verifying the calculations still work and all of the final items such as tags, signs, fire alarm panel.
|
BLD18-01628
| FIRE-Final Inspection | 11/14/2018 | 11/14/2018 | 11/14/2018 2:20:17 PM | P | FAIL |
|
|
Missing all of the small documents, missing occupant load sign, it appears west exit door can remain locks so the exit sign will need to be removed, plans show emergency lighting in the kitchen, restrooms and restroom corridor, provide fire extinguisher as discussed, provide duct smoke detectors as per the mechanical sheets and the fire alarm sheet, provide full fire alarm notifcation as per the engineered plans, provide clearance at outside patio as shown on the plans
Vince Phone #: ###-####
|
BLD17-04482
| FIRE-Final Inspection | 11/14/2018 | 11/14/2018 | 11/14/2018 12:18:12 PM | A | CANC |
|
|
Need the project related fire alarm permit addressed prior to a fire life safety inspection
Phone #: ###-#### Inspection requested via web by Darius Saxton
|
BLD18-01779
| FIRE-Conference | 11/13/2018 | 11/14/2018 | 11/14/2018 12:17:27 PM | A | DONE |
|
|
We spoke about doing phase sign offs for this area of work. Call Darius when on site, please Phone #: ###-#### Inspection requested via web by Ami Ostrow
|
BLD17-04278
| FIRE-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 11:58:34 AM | A | CANC |
|
|
Need the project related fire alarm permit addressed prior to a life safety inspection.
Jeff Phone #: ###-####
|
BLD18-02709
| FIRE-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 11:07:01 AM | A | PART |
|
|
A temporary for life safety is being given with Ron's approval until the racking permit is addressed. Also high piled storage is an issue at this time with plastics exceeding 6'. I'm also have the fire alarm contractor add a horn/strobe in an Office turned Conference Room.
|
FIR18-00767
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 11:05:06 AM | A | PART |
|
|
A temporary for this fire alarm permit is being given until a horn/strobe is added in the Conference Room. Room was originally a office but the use has changed.
|
FIR18-00670
| INSP-Sprinkler Rough-in | 11/13/2018 | 11/14/2018 | 11/14/2018 9:28:18 AM | A | FAIL |
|
|
Inspection was for the side sammys so that the cover could be repaired. The first side sammy I checked the retaining nut was bearly on.
Please call Chris Ford for above ground rough in Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00516
| INSP-Final Inspection | 11/14/2018 | 11/14/2018 | 11/14/2018 9:12:45 AM | P | PASS |
|
|
permit finaled
Please call 1/2 hour before arriving.Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00516
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 8:02:03 AM | A | FAIL |
|
|
Tool owner/operator was not available.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00733
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 7:44:13 AM | A | PASS |
|
|
Permit finaled
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00683
| INSP-Final Inspection | 11/8/2018 | 11/14/2018 | 11/14/2018 7:43:36 AM | A | PASS |
|
|
Permit finaled
|
FIR18-00700
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 7:36:33 AM | A | CANC |
|
|
Dave Phone #: ###-#### Inspection cancelled from web by: david davis
|
FIR16-00563
| INSP-Sprinkler Rough-in | 11/14/2018 | 11/14/2018 | 11/14/2018 12:00:00 AM | P | PASS |
|
|
Forward Flow test passed. TVFP is providing a more permanent solution for yearly testing.
coordinate forward flow of the back flow with Troy Nelson Phone #: ###-#### >> Inspection requested via web by Christophe Wilson
|
BLD16-02008
| FIRE-Final Inspection | 11/14/2018 | 11/14/2018 | 11/14/2018 12:00:00 AM | P | FAIL |
|
|
see fire inspection comments in documents 11-14-18TCO Phase 1 inspection. Review items from walk yesterday with Ron. Please call Adam when heading to site. ###-####.Thanks. AKJ Phone #: ###-#### >> Inspection requested via web by Adam Johnson
|
FIR18-00548
| INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/13/2018 9:25:31 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|