Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00546 INSP-Final Inspection11/13/201811/14/201811/15/2018 2:41:33 PMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Connie Danes
BLD17-03648 FIRE-Final Inspection11/13/201811/14/201811/14/2018 4:50:24 PMPFAIL
Life safety will be ok to final when the project related fire alarm and fire sprinkler permit is addressed.

Tony Phone #: ###-####
FIR18-00414 INSP-Final Inspection11/13/201811/14/201811/14/2018 4:49:05 PMAFAIL
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00333 INSP-Final Inspection11/13/201811/14/201811/14/2018 4:48:37 PMPFAIL
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten


Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD15-02318 FIRE-Final Inspection10/26/201811/14/201811/14/2018 3:05:55 PMPPASS
life safety passed

Please call ahead for access - Cody Phone #: ###-####
BLD15-02316 FIRE-Final Inspection10/26/201811/14/201811/14/2018 3:05:15 PMPPASS
life safety passed


Please call ahead for access - Cody Phone #: ###-####
FIR18-00298 INSP-Sprinkler Rough-in11/13/201811/14/201811/14/2018 2:51:25 PMPPASS
The additional hangers have been added. Will verify the 4 way brace at the riser during the final. All piping can be covered. Still need submittals verifying the calculations still work and all of the final items such as tags, signs, fire alarm panel.
BLD18-01628 FIRE-Final Inspection11/14/201811/14/201811/14/2018 2:20:17 PMPFAIL
Missing all of the small documents, missing occupant load sign, it appears west exit door can remain locks so the exit sign will need to be removed, plans show emergency lighting in the kitchen, restrooms and restroom corridor, provide fire extinguisher as discussed, provide duct smoke detectors as per the mechanical sheets and the fire alarm sheet, provide full fire alarm notifcation as per the engineered plans, provide clearance at outside patio as shown on the plans

Vince Phone #: ###-####
BLD17-04482 FIRE-Final Inspection11/14/201811/14/201811/14/2018 12:18:12 PMACANC
Need the project related fire alarm permit addressed prior to a fire life safety inspection

Phone #: ###-#### Inspection requested via web by Darius Saxton
BLD18-01779 FIRE-Conference11/13/201811/14/201811/14/2018 12:17:27 PMADONE
We spoke about doing phase sign offs for this area of work.
Call Darius when on site, please Phone #: ###-#### Inspection requested via web by Ami Ostrow
BLD17-04278 FIRE-Final Inspection11/13/201811/14/201811/14/2018 11:58:34 AMACANC
Need the project related fire alarm permit addressed prior to a life safety inspection.

Jeff Phone #: ###-####
BLD18-02709 FIRE-Final Inspection11/13/201811/14/201811/14/2018 11:07:01 AMAPART
A temporary for life safety is being given with Ron's approval until the racking permit is addressed. Also high piled storage is an issue at this time with plastics exceeding 6'. I'm also have the fire alarm contractor add a horn/strobe in an Office turned Conference Room.
FIR18-00767 INSP-Final Inspection11/13/201811/14/201811/14/2018 11:05:06 AMAPART
A temporary for this fire alarm permit is being given until a horn/strobe is added in the Conference Room. Room was originally a office but the use has changed.
FIR18-00670 INSP-Sprinkler Rough-in11/13/201811/14/201811/14/2018 9:28:18 AMAFAIL
Inspection was for the side sammys so that the cover could be repaired. The first side sammy I checked the retaining nut was bearly on.

Please call Chris Ford for above ground rough in Phone #: ###-#### Inspection requested via web by Jessia Maxwell
FIR18-00516 INSP-Final Inspection11/14/201811/14/201811/14/2018 9:12:45 AMPPASS
permit finaled

Please call 1/2 hour before arriving.Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00516 INSP-Final Inspection11/13/201811/14/201811/14/2018 8:02:03 AMAFAIL
Tool owner/operator was not available.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00733 INSP-Final Inspection11/13/201811/14/201811/14/2018 7:44:13 AMAPASS
Permit finaled

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00683 INSP-Final Inspection11/8/201811/14/201811/14/2018 7:43:36 AMAPASS
Permit finaled
FIR18-00700 INSP-Final Inspection11/13/201811/14/201811/14/2018 7:36:33 AMACANC
Dave Phone #: ###-#### Inspection cancelled from web by: david davis
FIR16-00563 INSP-Sprinkler Rough-in11/14/201811/14/201811/14/2018 12:00:00 AMPPASS
Forward Flow test passed. TVFP is providing a more permanent solution for yearly testing.


coordinate forward flow of the back flow with Troy Nelson Phone #: ###-#### >> Inspection requested via web by Christophe Wilson
BLD16-02008 FIRE-Final Inspection11/14/201811/14/201811/14/2018 12:00:00 AMPFAIL
see fire inspection comments in documents 11-14-18TCO Phase 1 inspection. Review items from walk yesterday with Ron. Please call Adam when heading to site. ###-####.Thanks. AKJ Phone #: ###-#### >> Inspection requested via web by Adam Johnson
FIR18-00548 INSP-Final Inspection11/13/201811/14/201811/13/2018 9:25:31 AMACANC
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus