Inspections for the day of: Thursday, November 15, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01730 FIRE-Final Inspection11/13/201811/15/201811/15/2018 2:56:00 PMPPASS
Life safety passed. Contractro agreed to provide ADA hardware on the pocket door and provide sticker at the main exit door with the keyed egress hardware.

Mark Phone #: ###-####
BLD18-03557 FIRE-Final Inspection11/15/201811/15/201811/15/2018 2:41:02 PMPPASS
Life safety passed. I verified with Tim that the reduces isle width did not change anything for the overhead sprinkler design.

Tony Phone #: ###-####
FIR18-00560 INSP-Sprinkler Rough-in11/15/201811/15/201811/15/2018 1:50:09 PMPPASS
See the city approved plans for locations marked "ok" where piping can be covered.

Rick Phone #: ###-####
NAF18-00113 INSP-Final11/14/201811/15/201811/15/2018 1:47:19 PMADONE
Life safety passed

Call prior to going Phone #: 2088695205 >> Inspection requested via mobile web by Paula Lambert
NAF18-00133 INSP-Sprinkler Rough-in11/15/201811/15/201811/15/2018 12:54:01 PMPPASS
Underground supply piping rough-in passed. Piping can be covered.


Troy, will call when completed this morning. Phone #: ###-#### Inspection requested via web by Daniel Buccino
BLD18-03318 FIRE-Final Inspection11/13/201811/15/201811/15/2018 11:29:24 AMAFAIL
Repair the exit signs and emergency lights.

Ashley Phone #: ###-####
FIR18-00546 INSP-Final Inspection11/14/201811/15/201811/15/2018 10:59:30 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Connie Danes
BLD18-02793 FIRE-Final Inspection11/14/201811/15/201811/15/2018 10:36:50 AMAFAIL
Provide annual inspection for the fire extinguishers, repair the exit sign/emergency light at the rear door, remove the deadbolt at the rear door and provid ADA compliant single action hardware.

Brayden Phone #: ###-####
BLD17-04278 FIRE-Final Inspection11/14/201811/15/201811/15/2018 10:08:48 AMAFAIL
Need the project related fire alarm permit finaled, need thumbturn removed from main exit and sticker installed at main exit, need emergency lighting repaired.

Jeff Phone #: ###-####
FIR18-00561 INSP-Final Inspection11/14/201811/15/201811/15/2018 10:07:58 AMAFAIL
As-builts are needed showing the additional devices as per the engineered plans and field conditions. A weather proof back box is needed in the basement shower. The NAC panel has been relocated to the ground floor. The FACP in the end of line calculations is not the panel installed. No actual testing performed.

Coltin Phone #: ###-####
BLD17-03648 FIRE-Final Inspection11/14/201811/15/201811/15/2018 9:08:15 AMAPASS
life safety passed

Tony Phone #: ###-####
FIR18-00333 INSP-Final Inspection11/14/201811/15/201811/15/2018 9:06:57 AMPPASS
permit finaled


Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR18-00414 INSP-Final Inspection11/14/201811/15/201811/15/2018 9:06:00 AMAPASS
permit finaled


Jordan Fuger Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-04482 FIRE-Final Inspection11/14/201811/15/201811/15/2018 8:14:27 AMAFAIL
There are still sync issues with the notification devices.

Phone #: ###-#### Inspection requested via web by Ami Ostrow
BLD17-04482 FIRE-Alarm Testing11/14/201811/15/201811/15/2018 8:13:49 AMAFAIL
There are still sync'ing issues with the notification devices.

Please call Darius Phone #: ###-#### Inspection requested via web by Ami Ostrow