Inspections for the day of: Friday, November 16, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03833 FIRE-Final Inspection11/16/201811/16/201811/16/2018 4:10:00 PMPPART
A temporary until Monday is ok so that panic hardware can be installed on the front/east side doors. Hardware to be removed from the front/west side doors. Building inspector and I discussed this as well as plan review (Carl). All other life safety items, fire sprinkler and fire alarm are passed.

Carson Phone #: ###-####
BLD18-03318 FIRE-Final Inspection11/15/201811/16/201811/16/2018 2:11:02 PMPPASS
Life safety passed

Please call ahead for access - Ashley Phone #: ###-####
FIR18-00488 INSP-Final Inspection11/16/201811/16/201811/16/2018 2:02:07 PMPPASS
Permit finaled
FIR18-00462 INSP-Final Inspection11/16/201811/16/201811/16/2018 2:01:43 PMPPASS
Permit finaled
FIR18-00566 INSP-Alarm Testing11/16/201811/16/201811/16/2018 1:44:14 PMPDONE
For todays inspection I only verified device locations. I noted smoke detectors needing centered on the door on the classroom side. Per a later phone call from Lee these detectors are ok to be deleted as long as the distance from the header to the ceiling does not exceed 24". I also noted many strobes that are overspaced in nearly every classroom and atleast one in the main corridor. I noted that the communication means being used is not what is shown on the approved plans. As-builts will be required but possibly for plan mods.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
BLD17-04278 FIRE-Final Inspection11/15/201811/16/201811/16/2018 11:33:08 AMAPART
A temporarty for life safety is ok with Ron's permission until the project related fire alarm permit is addressed.

Please call Jeff Fahey Phone #: ###-#### Inspection requested via web by Ami Ostrow
FIR18-00561 INSP-Final Inspection11/15/201811/16/201811/16/2018 11:32:24 AMAPART
A temporary for this permit is ok with Ron's permission until the weather proof backbox is installed. All other items are ok.

Coltin Phone #: ###-####
BLD18-03522 FIRE-Final Inspection11/15/201811/16/201811/16/2018 9:31:32 AMAPASS
life safety passed


Please call Shane for final inspection Phone #: ###-#### Inspection requested via web by Paul Saucerman