BLD18-02261
| FIRE-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 3:11:34 PM | P | PASS |
|
|
Life safety passed.
Jeff Phone #: ###-####
|
BLD19-02562
| FIRE-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 1:38:35 PM | P | FAIL |
|
|
Provide approved single action hardware for the IT Room and Storage Room doors. Provide panic hardware, per approved plans, for the main exit or receive plan review approval to utilize what is there. Please call ahead for access .5hr if possible - Rob Thornton Phone #: ###-####
|
BLD19-04497
| FIRE-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 1:36:46 PM | P | PASS |
|
|
Life safety passed. Card signed.
Dixon Phone #: ###-####
|
FIR18-00886
| INSP-Sprinkler Rough-in | 11/18/2019 | 11/19/2019 | 11/19/2019 12:08:21 PM | P | CANC |
|
|
Contact Hunter Anderson ###-#### 30 min prior to RTC Insp start please
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
BLD18-03906
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 11:41:42 AM | P | FAIL |
|
|
Provide annual inspection for the fire sprinkler system and fire extinguishers. Provide interconnect of the door mags and the fire alarm system as per the iFC. This work requires permit.
Call me when you’re headed this way. Phone #: ###-#### Inspection requested via web by Bob Thornton
|
FIR19-00492
| INSP-Supply line flush | 11/18/2019 | 11/19/2019 | 11/19/2019 11:04:21 AM | A | CANC |
|
|
George Jess will be the contact. Stacy Stuart has been contacted and will be on site at 930 AM so please meet him at this time. Thanks for all you do and I hope you have a great day! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00818
| INSP-Supply line flush | 11/18/2019 | 11/19/2019 | 11/19/2019 11:03:54 AM | A | CANC |
|
|
Cancel per Troy. U.G. cover Troy Nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD19-02583
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 10:21:06 AM | A | FAIL |
|
|
Provide plan modifications showing the actual use of the Open Office area and the basement. There is currently 42 chairs set up in the open office area for use as music/performance and the basement is being used as storage. Also provide single action hardware on all doors as discussed. Provide and mount the fire extinguishers upstairs and downstairs as discussed. Brandon- Phone #: ###-####
|
FIR19-00752
| INSP-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 10:07:26 AM | A | PASS |
|
|
Permit finaled. The underground supply line flush and hydro witnessed. . Troy Nelson Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR19-00748
| INSP-Supply line flush | 11/18/2019 | 11/19/2019 | 11/19/2019 10:05:55 AM | A | PASS |
|
|
The underground flush witnessed.
Troy Nelson Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD19-03533
| FIRE-Final Inspection | 11/18/2019 | 11/19/2019 | 11/19/2019 8:48:46 AM | A | PASS |
|
|
Life safety passed. Fire extinguisher to be placed as discussed prior to the building inspection.
Thanks,
Todd Phone #: ###-#### Inspection requested via web by Todd Kurns
|