Inspections for the day of: Thursday, November 2, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04280 FIRE-Final Inspection11/1/201711/2/201711/2/2017 2:58:46 PMPFAIL
Corrections have been made except as per plan review exit signs are required at the gates in the pool area.

Noah Phone #: ###-####
BLD17-03697 FIRE-Final Inspection11/2/201711/2/201711/2/2017 2:54:31 PMPFAIL
The existing sprinkler pendants are overspaced in atleast four locations and will need modified. I also noted that I would need to verify the hardware on the two new doors when installed. The annual inspection for the sprinkler system is current.
FIR17-00433 INSP-Sprinkler Rough-in11/2/201711/2/201711/2/2017 12:28:12 PMPPART
Todays inspection was for the sprinkler piping located in the combustible concealed spaces located on the roof. I was unable to get access to the areas where the dry sprig-ups have been installed. The other areas where the piping is installed I was able to inspect and found that one seismic restraint is needed. But the bigger issue is that all of this piping is supplied from the wet system and the areas where it is installed in unheated. Means to heat these areas are needed as per NFPA 13 or a dry pipe system may be required also per NFPA 13.
FIR17-00617 INSP-Supply line flush11/1/201711/2/201711/2/2017 11:12:17 AMPCANC
CALL LONNIE w/TVFP.
NEED THIS UNDERGROUND FLUSHED Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt Inspection cancelled from web by: Brad Bettencourt
BLD17-03831 FIRE-Final Inspection10/23/201711/2/201711/2/2017 10:30:06 AMAPASS
life safety passed

Tsering Phone #: ###-####
FIR17-00617 INSP-Sprinkler Rough-in11/1/201711/2/201711/2/2017 9:11:35 AMAPASS
The remaining underground supply piping is ok to cover.
BLD05-02431 FIRE-Final Inspection11/1/201711/2/201711/2/2017 6:25:15 AMAPASS
life safety passed.

Pat Phone #: ###-####
BLD17-03912 FIRE-Final Inspection11/1/201711/2/201711/1/2017 12:47:54 PMAPASS
Life safety passed.

Jense Phone #: ###-####