BLD16-04280
| FIRE-Final Inspection | 11/1/2017 | 11/2/2017 | 11/2/2017 2:58:46 PM | P | FAIL |
|
|
Corrections have been made except as per plan review exit signs are required at the gates in the pool area.
Noah Phone #: ###-####
|
BLD17-03697
| FIRE-Final Inspection | 11/2/2017 | 11/2/2017 | 11/2/2017 2:54:31 PM | P | FAIL |
|
|
The existing sprinkler pendants are overspaced in atleast four locations and will need modified. I also noted that I would need to verify the hardware on the two new doors when installed. The annual inspection for the sprinkler system is current.
|
FIR17-00433
| INSP-Sprinkler Rough-in | 11/2/2017 | 11/2/2017 | 11/2/2017 12:28:12 PM | P | PART |
|
|
Todays inspection was for the sprinkler piping located in the combustible concealed spaces located on the roof. I was unable to get access to the areas where the dry sprig-ups have been installed. The other areas where the piping is installed I was able to inspect and found that one seismic restraint is needed. But the bigger issue is that all of this piping is supplied from the wet system and the areas where it is installed in unheated. Means to heat these areas are needed as per NFPA 13 or a dry pipe system may be required also per NFPA 13.
|
FIR17-00617
| INSP-Supply line flush | 11/1/2017 | 11/2/2017 | 11/2/2017 11:12:17 AM | P | CANC |
|
|
CALL LONNIE w/TVFP. NEED THIS UNDERGROUND FLUSHED Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt Inspection cancelled from web by: Brad Bettencourt
|
BLD17-03831
| FIRE-Final Inspection | 10/23/2017 | 11/2/2017 | 11/2/2017 10:30:06 AM | A | PASS |
|
|
life safety passed
Tsering Phone #: ###-####
|
FIR17-00617
| INSP-Sprinkler Rough-in | 11/1/2017 | 11/2/2017 | 11/2/2017 9:11:35 AM | A | PASS |
|
|
The remaining underground supply piping is ok to cover.
|
BLD05-02431
| FIRE-Final Inspection | 11/1/2017 | 11/2/2017 | 11/2/2017 6:25:15 AM | A | PASS |
|
|
life safety passed.
Pat Phone #: ###-####
|
BLD17-03912
| FIRE-Final Inspection | 11/1/2017 | 11/2/2017 | 11/1/2017 12:47:54 PM | A | PASS |
|
|
Life safety passed.
Jense Phone #: ###-####
|