Inspections for the day of: Friday, November 2, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02771 FIRE-Final Inspection10/30/201811/2/201811/2/2018 2:20:24 PMACANC
Please call ahead for access - David Phone #: ###-####
BLD18-01505 FIRE-Final Inspection11/1/201811/2/201811/2/2018 2:00:07 PMAFAIL
Provide racking permit or remove the rackd as discussed, remove the thumbturn deadbolts on the main exit doors, provide stickers at the main exit doors, provide the missing exit light to the second exit corridor, provide exit discharge lights at all three exit doors as per the approved plans, repair the exit sign at the rear exit door, provide 4" min. address numbers


call for access- Kent Phone #: ###-####
BLD17-04370 FIRE-Final Inspection10/31/201811/2/201811/2/2018 1:28:07 PMAFAIL
Provide revised plans showing all racking requiring permits, provide sprinkler protection of the columns in the double row racking as per NFPA 13 16.1.4

Inspection requested via web by Jeff Higgins
FIR18-00803 INSP-Final Inspection10/31/201811/2/201811/2/2018 10:30:13 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00548 INSP-Final Inspection11/2/201811/2/201811/2/2018 10:28:34 AMPPART
Sprinkler work passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306
BLD17-02477 FIRE-Final Inspection11/1/201811/2/201811/2/2018 10:28:02 AMAPART
Life safety passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306

Cody Phone #: ###-####
GRD18-00033 FIRE-Final Inspection11/1/201811/2/201811/2/2018 10:24:14 AMAPASS
Life safety passed. Plan review approved gravel fire dept access roadway

John Phone #: ###-####
BLD17-02704 FIRE-Final Inspection11/1/201811/2/201811/2/2018 7:17:06 AMAPASS
Life safety passed

Mark Phone #: ###-####