BLD18-02771
| FIRE-Final Inspection | 10/30/2018 | 11/2/2018 | 11/2/2018 2:20:24 PM | A | CANC |
|
|
Please call ahead for access - David Phone #: ###-####
|
BLD18-01505
| FIRE-Final Inspection | 11/1/2018 | 11/2/2018 | 11/2/2018 2:00:07 PM | A | FAIL |
|
|
Provide racking permit or remove the rackd as discussed, remove the thumbturn deadbolts on the main exit doors, provide stickers at the main exit doors, provide the missing exit light to the second exit corridor, provide exit discharge lights at all three exit doors as per the approved plans, repair the exit sign at the rear exit door, provide 4" min. address numbers
call for access- Kent Phone #: ###-####
|
BLD17-04370
| FIRE-Final Inspection | 10/31/2018 | 11/2/2018 | 11/2/2018 1:28:07 PM | A | FAIL |
|
|
Provide revised plans showing all racking requiring permits, provide sprinkler protection of the columns in the double row racking as per NFPA 13 16.1.4
Inspection requested via web by Jeff Higgins
|
FIR18-00803
| INSP-Final Inspection | 10/31/2018 | 11/2/2018 | 11/2/2018 10:30:13 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00548
| INSP-Final Inspection | 11/2/2018 | 11/2/2018 | 11/2/2018 10:28:34 AM | P | PART |
|
|
Sprinkler work passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306
|
BLD17-02477
| FIRE-Final Inspection | 11/1/2018 | 11/2/2018 | 11/2/2018 10:28:02 AM | A | PART |
|
|
Life safety passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306
Cody Phone #: ###-####
|
GRD18-00033
| FIRE-Final Inspection | 11/1/2018 | 11/2/2018 | 11/2/2018 10:24:14 AM | A | PASS |
|
|
Life safety passed. Plan review approved gravel fire dept access roadway
John Phone #: ###-####
|
BLD17-02704
| FIRE-Final Inspection | 11/1/2018 | 11/2/2018 | 11/2/2018 7:17:06 AM | A | PASS |
|
|
Life safety passed
Mark Phone #: ###-####
|