Inspections for the day of: Tuesday, November 20, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00672 INSP-Sprinkler Rough-in11/19/201811/20/201811/20/2018 1:49:27 PMPCANC
Not ready. To be rescheduled.

Todd Ketterling is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00566 INSP-Alarm Testing11/19/201811/20/201811/20/2018 11:54:11 AMADONE
Today we tested the interconnection of the existing fire alarm devices with the new panel. All devices on the existing risers functioned except the "low air" pressure switch on the System #1 did not function. It will need to be replaced asap as discussed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
NAF17-00079 INSP-Final11/19/201811/20/201811/20/2018 11:52:38 AMAFAIL
Provide one hour assembly for the Gas Room, mount the fire extinguisher as discussed, provide single action hardware on both the front exit doors, provide ADA hardware for the RestRoom pocket door.

Call prior to going Phone #: 2089413696 >> Inspection requested via mobile web by Bob
FIR18-00592 INSP-Sprinkler Rough-in11/19/201811/20/201811/20/2018 11:21:58 AMAPASS
See the city approved plans for locations where piping can be covered that are marked "ok"

Contact Ken Orahood ###-#### 30 Min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00071 INSP-Final11/20/201811/20/201811/20/2018 11:21:16 AMPDONE
Life safety passed.

Call prior to going Phone #: 2088699271 >> Inspection requested via mobile web by Zack