FIR19-00744
| INSP-Alarm Testing | 11/4/2019 | 11/4/2019 | 11/5/2019 6:28:18 AM | P | PASS |
|
|
Permit finaled.
John Phone #: ###-####
|
BLD19-02934
| FIRE-Conference | 11/4/2019 | 11/4/2019 | 11/4/2019 2:26:57 PM | P | DONE |
|
|
Please call 30 minutes in advance Phone #: ###-#### Inspection requested via web by Chase Cheverton
|
FIR17-00603
| INSP-Sprinkler Rough-in | 11/1/2019 | 11/4/2019 | 11/4/2019 2:18:01 PM | P | CANC |
|
|
Todd Ketterling is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-04246
| FIRE-Final Inspection | 11/4/2019 | 11/4/2019 | 11/4/2019 1:26:47 PM | P | FAIL |
|
|
Provide the annual inspection for the fire extinguisher, repair or remove the non-functioning exit light, provide coveres that are missing on the electrical outlets, repair the non-functioning fire alarm system or provide permit for a demo of it.
Jennifer Phone #: ###-####
|
FIR19-00365
| INSP-Sprinkler Rough-in | 11/1/2019 | 11/4/2019 | 11/4/2019 1:07:26 PM | P | PASS |
|
|
See the city approved plans for area of rogh-in today.
Kenny Caldwell is the field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00353
| INSP-Sprinkler Rough-in | 11/4/2019 | 11/4/2019 | 11/4/2019 12:18:46 PM | P | PART |
|
|
The remainging tenting is passed on the 4th floor except for room 406 which needs the insulation modified. So all room piping can be covered except room 406.
Eric is the contact. it is to look at the west side 3rd and 4th thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
|
BLD19-04221
| FIRE-Final Inspection | 11/4/2019 | 11/4/2019 | 11/4/2019 10:56:34 AM | P | FAIL |
|
|
Repair or remove the non-functional exit signs and emergency lights. Provide the fire extinguisher as discussed.
Call ahead - Andrea is in Meridian Phone #: ###-####
|
FIR19-00744
| INSP-Final Inspection | 11/1/2019 | 11/4/2019 | 11/4/2019 10:31:06 AM | A | FAIL |
|
|
Everything works except the duct smoke detectors are not ready for testing. As-builts needed showing the additional 15cd strobe in the corridor.
|
NAF18-00096
| INSP-Sprinkler Rough-in/Hydro | 11/4/2019 | 11/4/2019 | 11/4/2019 9:17:59 AM | A | PASS |
|
|
Life safety passed. No fire alarm.
John ###-####
|
NAF19-00063
| INSP-Final | 11/4/2019 | 11/4/2019 | 11/4/2019 8:58:15 AM | A | DONE |
|
|
Life safety passed.
Call for access Phone #: 2086315442 >> Inspection requested via mobile web by Owner
|
BLD19-04221
| FIRE-Final Inspection | 10/31/2019 | 11/4/2019 | 11/4/2019 8:22:21 AM | A | FAIL |
|
|
Left message on voice mail. Went to job site but doors are locked. No inspection performed.
Ryan-please call for access Phone #: ###-####
|
BLD19-04246
| FIRE-Final Inspection | 11/1/2019 | 11/4/2019 | 11/4/2019 8:06:30 AM | A | FAIL |
|
|
I left a message on contacts voice mail that I was on the way. Went to project site but all doors locked. No inspection performed.
jENNIFER Phone #: ###-####
|