Inspections for the day of: Monday, November 5, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02643 FIRE-Final Inspection11/1/201811/5/201811/5/2018 3:23:10 PMPFAIL
Plans now on site, need fire alarm notification modified as discussed, need to hang fire extinguisher and repair the exit sign.

lynn Phone #: ###-####
FIR18-00654 INSP-Sprinkler Rough-in/Hydro11/2/201811/5/201811/5/2018 2:56:06 PMPPASS
The remaining length of underground is ok for cover. Plans need to be resubmitted showing the new underground pipe routing. Also I spoke with the contractor about possible bury depth issues as previously noted.


Please call Clarncce Phone #: ###-#### Inspection requested via web by Jessia Maxwell
BLD18-03908 FIRE-Final Inspection11/5/201811/5/201811/5/2018 2:41:02 PMPFAIL
Repair the existing fire alarm panel, provide annual inspection for the fire extinguishers and the existing fire sprinkler system, provide sprinkler modifications for the printing area on the first floor Lobby area.

Bryan Phone #: ###-####
FIR18-00570 INSP-Final Inspection11/4/201811/5/201811/5/2018 2:19:07 PMACANC
We received the ROC but as-builts have not been provided. Ken will have finished tonight and submitted tomorrow.

Phone #: ###-#### Inspection requested via web by Ken Webster
BLD18-03947 FIRE-Final Inspection11/5/201811/5/201811/5/2018 1:53:15 PMPPASS
life safety passed. Plan review approved the new exit path.

Steve Phone #: ###-####
FIR18-00617 INSP-Sprinkler Rough-in11/5/201811/5/201811/5/2018 1:44:26 PMPPASS
See the city approved plans for piping marked "ok" that can be covered in the Kitchen area.

Rough to Cover inspection for Phase 2. Foreman is Zack Grasmick Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR17-00708 INSP-Final Inspection11/2/201811/5/201811/5/2018 12:25:11 PMACANC
Todd wants to reschedule for tomorrow when he has fittings to set off the flow switch.Todd Phone #: ###-####
FIR18-00738 INSP-Sprinkler Rough-in/Hydro11/5/201811/5/201811/5/2018 11:52:45 AMPCANC
Scheduled for the wrong day.

Hydro Test for 8" UG.

Please call Troy with time frame. Thanks Phone #: ###-#### Inspection requested via web by Jeff Packham
FIR18-00702 INSP-Final Inspection11/5/201811/5/201811/5/2018 11:34:56 AMPCANC
To be rescheduled with life safety inspection per discussion with Tom.


We would like to perform this inspection in conjunction with the fire life safety final for the BLD permit.

Please call Tom with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD18-01505 FIRE-Final Inspection11/5/201811/5/201811/5/2018 11:06:36 AMPPASS
Life safety passed

Call half hour before to meet // Ken Phone #: ###-####
BLD18-04013 FIRE-Final Inspection11/2/201811/5/201811/5/2018 10:10:42 AMAPASS
Life safety passed

Tsering Phone #: ###-####
BLD17-03833 FIRE-Final Inspection11/2/201811/5/201811/5/2018 9:50:16 AMAFAIL
Not ready for final. Todays final was for approval for cover of the platform. It appears to have been completely filled with insulation and is ok for cover.


Clive Phone #: ###-####
BLD18-02771 FIRE-Final Inspection11/2/201811/5/201811/5/2018 9:49:09 AMAPASS
Life safety passed. The sticker at door and occupant load sign to be installed prior to a building inspeciton

Please call ahead for access - David Phone #: ###-####