Inspections for the day of: Friday, November 8, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00661 INSP-Sprinkler Rough-in11/7/201911/8/201911/8/2019 3:06:16 PMPCANC
Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00706 INSP-Final Inspection11/7/201911/8/201911/8/2019 3:06:02 PMPFAIL
Need as-builts submitted/approved and the new cover installed on the weather proof strobe. I did witness the function test of the notification devices.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00221 INSP-Sprinkler Rough-in/Hydro11/4/201911/8/201911/8/2019 1:25:29 PMAPART
hydro dry system witnessed with no pressure loss. I looked at the elevator lobby for the 2nd and 3rd floors and discussed with Tom and Adam about adding a head in the soffit opposite of the elevators. // Rick Phone #: ###-####
FIR19-00683 INSP-Final Inspection11/7/201911/8/201911/8/2019 1:00:36 PMAFAIL
No testing performed. The communicator needs to be installed in an area where it will meet its UL listing (temperature in this case). Also per the UL listing it needs to be installed in the same room and with-in 20'-0".

We would like this inspection to be performed at 9:00 am per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
BLD19-01952 FIRE-Final Inspection11/7/201911/8/201911/8/2019 10:45:17 AMAFAIL
Life safety will be ok to final when the exit discharge lighting is installed and tested.

Justin Phone #: ###-####
FIR19-00756 INSP-Sprinkler Rough-in11/8/201911/8/201911/8/2019 9:27:12 AMPFAIL
The area that was requested to be inspected is not shown on the city approved plan. Plan mods are needed showing all of the scope of work or another permit. No piping can be covered.

Inspection for west side of space. Phone #: ###-#### Inspection requested via web by Jonathan LaFond
FIR19-00713 INSP-Final Inspection11/7/201911/8/201911/8/2019 8:46:24 AMAFAIL
Panel is in trouble, also the batteries do not sit in correctly due to two conduits being installed in the bottom of the fire alarm panel, There is already signs of the wires being pinched by the batteries when the door is closed. No testing done.

Gary Phone #: ###-####
FIR19-00568 INSP-Final Inspection11/7/201911/8/201911/8/2019 7:31:57 AMAPASS
Permit finaled

Rick Phone #: ###-####