FIR19-00661
| INSP-Sprinkler Rough-in | 11/7/2019 | 11/8/2019 | 11/8/2019 3:06:16 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR19-00706
| INSP-Final Inspection | 11/7/2019 | 11/8/2019 | 11/8/2019 3:06:02 PM | P | FAIL |
|
|
Need as-builts submitted/approved and the new cover installed on the weather proof strobe. I did witness the function test of the notification devices.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
FIR19-00221
| INSP-Sprinkler Rough-in/Hydro | 11/4/2019 | 11/8/2019 | 11/8/2019 1:25:29 PM | A | PART |
|
|
hydro dry system witnessed with no pressure loss. I looked at the elevator lobby for the 2nd and 3rd floors and discussed with Tom and Adam about adding a head in the soffit opposite of the elevators. // Rick Phone #: ###-####
|
FIR19-00683
| INSP-Final Inspection | 11/7/2019 | 11/8/2019 | 11/8/2019 1:00:36 PM | A | FAIL |
|
|
No testing performed. The communicator needs to be installed in an area where it will meet its UL listing (temperature in this case). Also per the UL listing it needs to be installed in the same room and with-in 20'-0".
We would like this inspection to be performed at 9:00 am per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
BLD19-01952
| FIRE-Final Inspection | 11/7/2019 | 11/8/2019 | 11/8/2019 10:45:17 AM | A | FAIL |
|
|
Life safety will be ok to final when the exit discharge lighting is installed and tested.
Justin Phone #: ###-####
|
FIR19-00756
| INSP-Sprinkler Rough-in | 11/8/2019 | 11/8/2019 | 11/8/2019 9:27:12 AM | P | FAIL |
|
|
The area that was requested to be inspected is not shown on the city approved plan. Plan mods are needed showing all of the scope of work or another permit. No piping can be covered.
Inspection for west side of space. Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|
FIR19-00713
| INSP-Final Inspection | 11/7/2019 | 11/8/2019 | 11/8/2019 8:46:24 AM | A | FAIL |
|
|
Panel is in trouble, also the batteries do not sit in correctly due to two conduits being installed in the bottom of the fire alarm panel, There is already signs of the wires being pinched by the batteries when the door is closed. No testing done.
Gary Phone #: ###-####
|
FIR19-00568
| INSP-Final Inspection | 11/7/2019 | 11/8/2019 | 11/8/2019 7:31:57 AM | A | PASS |
|
|
Permit finaled
Rick Phone #: ###-####
|