FIR17-00390
| INSP-Final Inspection | 12/12/2018 | 12/13/2018 | 12/13/2018 2:25:17 PM | P | PASS |
|
|
Permit finaled
Call Matt Clark 30 Minutes before if possible. Phone #: ###-#### Inspection requested via web by jason petty
|
FIR17-00736
| INSP-Final Inspection | 12/12/2018 | 12/13/2018 | 12/13/2018 2:17:00 PM | P | PASS |
|
|
Permit finaled
Please call Matt Clark 30 minutes ahead if possible Phone #: ###-#### Inspection requested via web by jason petty
|
NAF18-00137
| INSP-Final | 12/13/2018 | 12/13/2018 | 12/13/2018 1:12:30 PM | P | FAIL |
|
|
Provide ADA approved single action hardware on the marked exit door.
Phone #: 2088307115 >> Inspection requested via mobile web by Vince
|
FIR18-00864
| INSP-Sprinkler Rough-in | 12/13/2018 | 12/13/2018 | 12/13/2018 12:55:08 PM | P | PASS |
|
|
Rough-in passed. All piping can be covered.
Mike Phone #: ###-####
|
FIR18-00709
| INSP-Final Inspection | 12/13/2018 | 12/13/2018 | 12/13/2018 12:05:03 PM | P | PASS |
|
|
Permit finaled
Jeremy Phone #: ###-####
|
BLD18-03987
| FIRE-Final Inspection | 12/12/2018 | 12/13/2018 | 12/13/2018 11:43:12 AM | A | PASS |
|
|
Life safety passed.
Jeff Phone #: ###-####
|
FIR18-00455
| INSP-Alarm Testing | 12/12/2018 | 12/13/2018 | 12/13/2018 11:31:23 AM | A | FAIL |
|
|
The inspection today was just for the third floor. Need horn added in the southwest corner. Need strobe in the Executive Break Room. Need all tampers and flow switches tested that effect the third floor and exit pass. Need elevators tested. Need plan mods showing address changes and different NAC panels being used.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00583
| INSP-Sprinkler Rough-in | 12/12/2018 | 12/13/2018 | 12/13/2018 11:28:55 AM | A | PASS |
|
|
This inspection was for the Area "C" Fitness Center. Piping can be covered. Per contractor the limited use of wood is fire rated.
Tony Phone #: ###-####
|
FIR18-00428
| INSP-Final Inspection | 12/12/2018 | 12/13/2018 | 12/13/2018 11:27:25 AM | A | FAIL |
|
|
All tile on the 3rd floor is installed but the path of egress on the second floor and first floor have sprinkler issues which include shipping caps still on pendants and lay-in tile missing. Per Jim the only tampers and flow switches tested have been for the second floor. Tony Phone #: ###-####
|
FIR18-00569
| INSP-Alarm Testing | 12/12/2018 | 12/13/2018 | 12/13/2018 8:24:35 AM | A | PART |
|
|
Only the four fire smoke dampers and the east side duct detector were tested today in the Gym. The west side hvac unit did not function.
Phone #: ###-#### Inspection requested via web by Ken Webster
|